5.4. Network Variable Description - VSD Profile - input5.4.1. Frequency Converter Speed SetpointVariable name: SNVT type: State: Value: Command:nviDrvSpeedStpt SNVT_switch 0 (False) Any Stop1 (True) 0 Running 0 %1 (True) 1-200 Running 0.5 to 100 %1 (True) 201-255 Running 100 %0xFF (default) Any AUTO (invalid, no action)This input variable provides start / stop control and a speed reference.5.5. Network Variable Description - VSD Profile - Output5.5.1. Drive SpeedVariablename:SNVTtype: Value:nvoDrvSpeed SNVT_lev_percent Min: Max: Resolution:-163.840 % +163.830 % 0.005 %This variable contains the frequency converter speed as a percentage of the nominal speed.5.5.2. Output CurrentVariablename:SNVTtype: Value:nvoDrvCurnt SNVT_amp Min: Max: Resolution:0 A 3,276.6 A 0.1 AThis variable contains the frequency converter output current in ampere measured as a meanvalue, IRMS.The value is filtered and therefore approximately 1.3 seconds delayed before a current change isreflected in the output variable.5.5.3. Output VoltageVariablename:SNVTtype: Value:nvoDrvVolt SNVT_volt Min: Max: Resolution:0 V 3,276.6 V 0.1 VThis variable contains the frequency converter output voltage.VLT® FC 100 LonWorks 5. Configuration of the systemMG.11.E1.02 - VLT® is a registered Danfoss trademark 375