5.6. Network Variable Description - VSD Profile - Con-figuration5.6.1. Max Motor Speed [%]Variablename:SNVTtype:Default val-ue: Min value: Max value:nciMaxSpeed SNVT_lev_percent 100 % 0 % 163.830 %This variable configures the maximum motor speed in % and associates it with par. 4-13MotorSpeed High Limit (par. 4-14 in Hz mode).The value is entered as a percent of nominal speed, as defined by the Nominal Speed (nciNml-Speed) configuration value.For more information on reference scaling, please refer to theHow to Control the FC 100 section.If a value higher than 163.830% is requested, use the parameter access command.5.6.2. Min Motor Speed [%]Variablename:SNVTtype:Default val-ue: Min value: Max value:nciMinSpeed SNVT_lev_percent 0 % 0 % 163.830 %This variable configures the minimum motor speed in % and associates it with par. 4-11MotorSpeed Low Limit (par. 4-12 in Hz mode).The value is entered as a percent of nominal speed, as defined by the Nominal Speed (nciNml-Speed) configuration value.For more information on reference scaling, please refer to theHow to Control the FC 100 section5.6.3. Nom Motor Speed [RPM]Variablename:SNVTtype: Default value: Min value: Max value:nciNmlSpeed SNVT_rpm 1420 RPM 10 RPM 65,534 RPMThis variable configures the nominal motor speed in RPM and associates it with par. 1-25MotorNominal Speed.NB!Please note that this variable can be adjusted only while the frequency converter isstopped.If a value lower than 10 RPM is entered, nciNmlSpeed will be set to 10 RPM.5.6.4. Nominal Motor Frequency [Hz]Variablename:SNVTtype: Default value: Min value: Max value:nciNmlFreq SNVT_freq_hz 50 Hz 20 Hz 100 HzThis variable configures the nominal motor frequency and associates it with par. 1-23Motor Nom-inal Frequency.VLT® FC 100 LonWorks 5. Configuration of the systemMG.11.E1.02 - VLT® is a registered Danfoss trademark 395