Page 18 iBootBar V1.5xDevice CommandsCommand Description Admin Fact Defaultget devices / get all / get outlets This command displays a list of connected devices, and their current status. Noget device <#1‐#16/devname> Get device information. Displays the device name, and all outlet names and currentstatusYes Dataprobeset device <#1‐#16 > name Set the name of the selected iBootBar. 20 characters max.get current Gets the measured current of the local iBootBar Yesget device <#1‐#16/devname> current Get the measured current of the selected iBootBarget cycle Get or set the cycle time in seconds. No 10set cycle <1‐99>get delay Get or set the delay time in seconds. No 1set delay <1‐99>get current alarm High and Low alarms are used to monitor current conditions and send an alert byemail, SNMP and syslog when the high or low thresholds are exceeded.From 0.0 to 10.0/15.0/20.0 (depending on max current for device) in 0.1 ampincrements. For devices with two Mains, Main A and Main B are set separately, butdisplayed together with the get command.Yes Highalarm:10.0 for 10 AmpModels15.0 for 15 AmpModels20.0 for 20 AmpModelsLowalarm:0.0 Ampget device <#1‐#16/devname> current alarmset main highalarm set device <#1‐#16/devname> main highalarm set main highalarm set device <#1‐#16/devname> main lowalarm