Dedicated Micros ©2011MI-I-ECO4/E1-278 Eco4Zone InputThis menu allows the configuration of established alarm zones. A single or multiple trigger can beused to generate an alarm. It is possible to allocate up to 32 alarm zones to carry out a combinationof actions. Use these options in conjunction with the Zone Actions menu.Entry time This is the number of seconds allowed for the user to enter thezone and disable the alarms. If the alarm is not disabled withinthis period the alarm will be triggered.Exit time This is the number of seconds from the alarm being set withinwhich the user must exit the set zone. If the user is still within thezone after this time period the alarm will be triggered.Zone A zone can be established to logically groups alarms and initiateactions when an alarm is activated, there are 32 configurablezones.Title This information is stored along with the relevant images in thedatabase, ensure this has relevance to the alarm zone.Pre-Alarm sec This is the time period prior to the start of the alarm includedwith the alarm recording for archive. These images will also beprotected from being overwritten.Note: It is recommended that the Pre-Alarm option be set to the same value as the Pre-Triggersetting in the “Profile Record“ menu. This will ensure successful playback of high qualityPre-Trigger images. High quality pre-trigger images will only playback properly if review(playback) starts prior to the pre-trigger initiation.Intelligent Security & Fire Ltd