8. Lug Hole Layout — Top terminal plate designed to use upto 0.50" dia. bolt and a maximum 1.75" centers and 1.188"min., 2 hole lug.9. Lug Attachment — Maximum of six cable lugs can beinstalled per terminal plate. Lug Hardware not included.10. Safety Shield Installation — Top terminal safety shieldconsists of three pieces. Assemble per the below illustra-tion. Clear plastic shields are of different lengths. Longershield to be installed on the front side of the terminal plate.The shields should be even at the bottom, making the frontshield longer at the top.Side TerminationConsult system layout diagram for side termination location.1. Remove safety shield bracket if required.2. Install plastic Side Terminal Bracket and re-install safetyshield bracket using bolts from previous step. Use 3/8-16x 1.50" bolt for the remaining bracket assembly. Boltsshould be installed loosely for future adjustments.3. Install side terminal connector to battery posts using 1/4-20 hardware plate to terminal plate bracket using 1/4-20x 1.00" hardware. Bolts should be installed loosely forfuture adjustments.110.881.393.753.75 .56 DIA. HOLES FOR1/2" BOLTSComplete Assembly