46 | OperationTable 6. Settings (continued)Description Default SettingAvailable SettingsReset Peak Headroom Watts [No] [Yes]If No, no action.If Yes, the Peak Headroom Watts value is clearedand the date and time stamp for this statistic is setto the current date and time.NoClear Event Log The number after “Total events” shows howmany events are currently stored in the log.Press the button for one second to resetthe event count to zero and clear the log.—LCD Contrast [-5], [-4], [-3], [-2], [-1], [+0], [+1], [+2], [+3],[+4], [+5]The LCD Contrast is adjustable and the valid rangeis from -5 to +5. This range covers the maximumadjustment for contrasting the background with thetext in the visual display of the control panel.[+0]Transferring the UPS Between ModesTransferring between modes includes: Transferring from Normal to Bypass mode Transferring from Bypass to Normal modeTransferring from Normal to Bypass ModeTo transfer from Normal to Bypass mode:1 Press the button for one second to go to the main menu selection and scroll down to theControl menu using the button.2 Press the button to enter the Control menu.3 Select Go to Bypass.The text on the screen changes to Manual Bypass Command Sent. The Bypass mode iconflashes, indicating Bypass mode.