IMPORTANTEnsure that all equipment connected to this panel is fully compatible.If in doubt, check with supplier or contact Technical Helpline.TECHNICAL SPECIFICATION1. INSTALLATIONThe panel should be installed in a clean, dry, reasonably well ventilated place, and not in direct sunlight.Temperatures in excess of 40°C may cause problems, contact technical help line for further information.The panel should be located away from any potential hazard, in a position where it is readily accessible to authorised staff andto the fire services, ideally on the perimeter of a building near a permanent entrance.When mounting the panel to the wall, do not drill through the fixing holes on the back plate, as this could allow brick dust tocontaminate the circuitry.Cable entry can be from rear or top, 20mm conduit entries are provided at top, cable entry aperture is provided at rear.Do not fit smoke detectors into bases until all building work likely to cause dust is complete.Smoke detectors are delicate and can be affected by dust and give false alarms, or slow response.It is essential that if smoke detectors are fitted prior to building work being complete, then protective covers or bags are usedto prevent dust entry.Installation Instructions for:4200 Series Fire Panels (8 Zone Version)8 ZONESupply Voltage 230Vac +10%,-15%Number of zones 8Nominal Current 40mABattery 1 x 12V 7 AHNo of sounder circuits 2Total sounder circuit load 800mA total maxSounder circuit EOL device 6K8 resistorDetector zone EOL device EOLM-1Number of detectors per zone 20 Max