9. COMMISSIONING THE SYSTEMAssuming that the installation instructions have been followed and successfully completed, then the complete fire alarm systemis now ready for commissioning.Test each detector and call point in turn to check that it operates the alarm correctly. Reset after each test. Check that all thesounders operate.10. WALK TESTA walk test function has been included in this panel to enable one person (i.e. the contractor/ installer) to test the fire alarmwithout an assistant. This function is for the sole use of the contractor/installer and not for normal operational use.The walk test access code is concealed inside the fire alarm control panel. Once the walk test code has been correctly enteredthe test in progress indicator will show and the buzzer will pulse, this sets a time window of 10 minutes. If a sensor is triggeredwithin this time the sounders will operate for a short time then the system will automatically reset.If a sensor is not triggered within this time duration then the system will automatically reset and return to normal operation.To end the walk test press reset.11. HANDOVERIf there is a delay in the occupation of the building and the fire alarm is not required, ensure that the battery is regularlycharged, otherwise it may be permanently damaged.The responsible person should be acquainted with the logbook check, test and operating procedures. Hand over the AccessCode keyfob to the responsible person.12. AFTER CAREDo not clean the panel exterior with solvent cleaners or harsh abrasives.13. FUSE REPLACEMENTRefer to fuse schedule on PCB for details of replacement fuses.14. TECHNICAL HELPLINEFor technical assistance contact our technical helpline. Tel 01302 303350CC1234-4-