3. MAINS CONNECTIONThe mains supply should be exclusive to the fire alarm as detailed in BS 5839 pt. 1. A plug and socket is not satisfactory.We recommend that a switched double pole fused spur unit is used and marked FIRE ALARM DO NOT SWITCH OFF, and thisshould be solely for the use of the fire alarm. This also provides a method of isolating the supply for maintenance purposes.The mains supply should only be connected to the terminal block marked MAINS.4. BATTERY CONNECTIONConnect the red battery wire to the red battery terminal (+), connect the black battery wire to the black battery terminal (-).5. CLASS CHANGEThe sounder circuits can be operated by an external volt free contact. A short circuit at this terminal will activate non-latchingsounders, (no indication will show on the fire alarm panel) This is sometimes used for schools at Class Change times.6. OUTPUTS6.1. FAULT RELAYThe fault relay provides a set of fused volt free changeover contacts, which operate in the event of a fault condition occurring,these contacts are not monitored.For connection details refer to connection diagram on page 2 or refer to PCB.6.2. FIRE RELAYThe fire relay provides a set of fused volt free changeover contacts, which operate in the event of a fire condition occurring,these contacts are not monitored.For connection details refer to connection diagram on page 2 or refer to PCB.7. RECOMMENDED CABLE TYPE AND SIZEMains Wiring:1.0mm2 - 1.5mm 2 Mineral insulated or similar fire proof cable.Zone Wiring:1.0mm 2 - 1.5mm 2 Mineral Insulated or similar fire proof cable.Sounder Wiring:1.0mm 2 - 2.5mm 2 Mineral Insulated or similar fire proof cable.INSTALLATION GUIDEDO NOT USE A HIGH VOLTAGE INSULATION TESTER WHEN WIRING IS CONNECTED TO ANY ELECTRONICEQUIPMENT.Do not use excessive force when tightening the screws on the terminal blocks.8. INSTALLATION CHECKPanel: With EOLM-1 fitted in the panel, connect the mains and battery and check that the green power on indicator is lit andno other indicators are showing.Check that the panel operates correctly by entering the correct access code, then silence, then reset, check that all the indicatorsshow momentarily.Zone circuits: Disconnect the mains and battery. Wire in the zone circuits one at a time, with the EOLM-1 transferred to theend of the zone (check polarity) but with no sensors plugged in.Power up the panel by connecting the mains and battery. Check that the panel indicates a zone fault. Check that the furthestcall point operates correctly by using one of the plastic test keys provided. (ie. the fire alarm goes into the fire condition).Reset the panel. Complete all zone circuits as above.Fit all detectors and check that the panel shows healthy (ie. No faults showing). If there is a problem, check the faulty circuitfor continuity, correct polarity and the polarity of the EOLM-1. DO NOT USE A HIGH VOLTAGE INSULATION TESTER.Sounder circuits: Disconnect the mains and battery. Wire in one of the sounder circuits transferring the end of line resistor,to the end sounder in that circuit.Power up the panel as before and verify that no fault shows. If there is a fault, check the circuit for continuity and polarity.DO NOT USE A HIGH VOLTAGE INSULATION TESTER.Repeat as above for next sounder circuit.Momentarily operate a call point using one of the plastic test keys provided, and check that all the sounders operate, and thefire indicator shows on the fire alarm control panel. Reset the panel.-3-