614-40095-00 161. Connect the input socket (48) on the HotSwap MBPmodule to the AC power source.2. Connect the UPS input power cord (13) to thereceptacle "UPS Input" (47) of the HotSwap MBPmodule.3. Connect the "UPS Output" cable (46) of the HotSwapMBP module to the outlet (3) of the UPS .4. Connect the equipment to the outlets (42) on theHotSwap MBP module.These outlets differ, depending on the version ofthe HotSwap MBP module.Caution : Do not use UPS outlets (4) to supplyequipment because use of switch (45) on the HotSwapMBP module would cut supply to the equipment.HotSwap MBP module operation The HotSwap MBP module has a rotary switch (45) withtwo positions:Normal : the load is supplied by the UPS, LED (43) is on.Bypass : the load is supplied directly by the AC powersource. LED (44) is on. Load is not protected.UPS start-up with the HotSwap MBP module1. Check that the UPS is correctly connected to the HotSwap MBP module.2. Start the UPS by pressing the button on the UPS control panel. LED (43) "UPS ON - OK to switch" on the HotSwapMBP module goes ON (otherwise, there is a connection error between the HotSwap MBP module and the UPS).3. Set switch (45) to Normal position. The red LED on the HotSwap MBP module goes OFF.HotSwap MBP module test1. Set switch (45) to Bypass position and check that the load is still supplied.2. Set switch (45) back to Normal position.