614-40095-00 194.3 Display functionsPress the Enter ( ⮠ ) button to activate the menu options. Use the two middle buttons (⯅ and ⯆) to scroll through themenu structure. Press the Enter (⮠ ) button to select an option. Press the (ESC) button to cancel or return to the previousmenu.Menu map for display functionsMain menu Submenu Display information or Menu functionMeasurements -Load: [Total Load/Load (Primary)/Load (Group 1)/Load (Group 2)] : W, A, VA, pF[Input/Output] : V, f[Efficiency] : %[Battery Info] : %, min, V, number of EBM, Age service, Age Warning[Average power usage] : Toal, Primary, Group 1, Group 2[Cumulative power] : Total, Since Primary, Since Group 1, Since Group 2ControlLoad SegmentsGroup 1: ON / OFFGroup 2: ON / OFFThese commands overrule user settings for load segments.Start battery test Starts a manual battery test (possible if load >20% and battery >80%)Change battery Disable charger, Replace battery, Update settingsConnectivity test Dry contacts test, Relay card test, Line failure test, Battery low testFunctions reset Reset fault state, Reset power usage, Reset battery life, Card reset, Restorefactory settingsSettingsLocal settings Sets product general parameters, see User settingsInput / outputsettings Sets input and output parametersON / OFF settings Sets ON / OFF conditionsBattery settings Sets battery configurationCommunicationsettingsSets communication parameters (input/output signals, remote signals, IPV4address)Event logView alarms Displays the alarms storedView events Displays the events storedView all Displays the faults and events storedReset all Clears the faults and events storedFault logView fault Displays the faults storedReset faults Clears faults