Eaton Power Xpert™ 9395P Sync Control Installation and Operation Manual P-164000502 Rev 1 3-1Chapter 3 InstallationW A R N I N G Only qualified service personnel (such as a licensed electrician) shall perform the electrical installation. Riskof electrical shock. Shut down all sources of power to the Eaton 9395P UPS or SSBM system before connecting the controlwiring to the Eaton Sync Control enclosure and UPS. Hazardous voltages exist inside the UPS or SSBM andin the Eaton Sync Control enclosure. Check all terminal conductors with a known serviceable voltmeter beforeconnecting the wiring.A V E R T I S S E M E N T ! Seul le personnel qualifié, comme les électriciens agréés, peut effectuer l’installation électrique. Risqued’électrocution. Couper toutes les sources d’alimentation de chaque UPS avant de connecter le câblage de commande àl’enveloppe du module Sync Control et à l’UPS d’Eaton. Des tensions dangereuses sont présentes dans l’UPSou le SSBM et dans l’enveloppe du Sync Control d’Eaton.Once the Eaton Sync Control has been moved to its installed location, unpacked, andinspected, it is ready for installation and wiring.Use the applicable procedure from the following list to install the Eaton Sync Controlto the UPS: With an Eaton 9395P UPS, proceed to paragraph 3.1. With an Eaton 9395 SSBM, proceed to paragraph 3.2.3.1 Installation and Wiring with an Eaton 9395P UPSNOTE When installing wiring connections, conduit must be installed between the Eaton Sync Control and theUPS cabinet.To install and wire:1. Install the Eaton Sync Control panel to the selected mounting location.See Figure 2‐1 on page 2-2 for mounting hole dimensions and Figure 2‐2 onpage 2-3 for conduit entrance locations.2. Unfasten the front door latches and swing the door open.3. Complete all control wiring interconnections using Table 3‐1 for wiringrequirements.Figure 3‐1 shows the Eaton Sync Control TB1 terminal block and ground terminallocations. Figure 3‐2 shows the TB1 terminal block wiring detail.Figure 3‐5 shows the typical locations of the UPS TB3, TB6, and X-Slot®Communication bays. Figure 3‐3 shows the TB6 detail.Refer to the applicable Eaton 9395P UPS Installation and Operation Manual listedin paragraph 1.3 on page 1-4 for UPS cabinet terminal locations and assignments,termination requirements, conduit landing locations, and terminal accessinstructions.Figure