Eaton 9395 UPS (225–275 kVA) Installation and Operation Manual 164201683 Rev 3 www.eaton.com/powerquality 3-1Chapter 3 UPS Installation Plan and UnpackingUse the following basic sequence of steps to install the UPS:1. Create an installation plan for the UPS system (Chapter 3).2. Prepare your site for the UPS system (Chapter 3).3. Inspect and unpack the UPS cabinet (Chapter 3).4. Unload and install the UPS cabinet, and wire the system (Chapter 4).5. Install features, accessories, or options, as applicable (Chapter 5).6. Complete the Installation Checklist (Chapter 4).7. Have authorized service personnel perform preliminary operational checks andstart up the system.NOTE Startup and operational checks must be performed by an authorized Eaton Customer ServiceEngineer, or the warranty terms specified on page W-1 become void. This service is offered as part of thesales contract for the UPS. Contact an Eaton service representative in advance (usually a two-week notice isrequired) to reserve a preferred startup date.3.1 Creating an Installation PlanBefore installing the UPS system, read and understand how this manual applies to thesystem being installed. Use the procedures and illustrations in paragraph 3.2 andChapter 4 to create a logical plan for installing the system.3.2 Preparing the SiteFor the UPS system to operate at peak efficiency, the installation site should meet theenvironmental parameters outlined in this manual. If the UPS is to be operated at analtitude higher than 1500m (5000 ft), contact an Eaton service representative forimportant information about high altitude operation. The operating environment mustmeet the weight, clearance, and environmental requirements specified.3.2.1 Environmental and Installation ConsiderationsThe UPS system installation must meet the following guidelines: The system must be installed on a level floor suitable for computer or electronicequipment. The system must be installed in a temperature and humidity controlled indoor areafree of conductive contaminants. The cabinet can be installed in line‐up‐and‐match or standalone configurations.Failure to follow guidelines may void your warranty.The UPS equipment operating environment must meet the weight requirementsshown in Table 3‐1 and the size requirements shown in Figure 3‐1 through Figure 3‐7.Dimensions are in millimeters (inches).Figure