UPS INSTALLATION PLAN AND UNPACKINGEaton Power Xpert 9395P UPS (300 kVA, 300 kW) Installation and Operation Manual P-164000563 Rev 1 www.eaton.com/powerquality3-10Terminals E1A through E5A and E9A through E11A are stud type terminals. Theintercabinet power wiring connections for this equipment are rated at 90°C. SeeTable 3‐7 for supplied intercabinet wiring terminal hardware.The torque values listed are the maximum allowable. Tightening further will riskbreaking or twisting the stud.Table 3‐6. UPS External Power Cable Terminations for the Single UPM Eaton 9395P-300/200 , Eaton 9395P-300/225, Eaton 9395P-300/250, Eaton9395P-300/275 and Eaton 9395P-300/300AC Input to UPS Rectifier E1 Phase A 4 – 2 bolt mounting 76 (56) M12E2 Phase B 4 – 2 bolt mounting 76 (56) M12E3 Phase C 4 – 2 bolt mounting 76 (56) M12AC Input to Bypass E6 Phase A 4 – 2 bolt mounting 76 (56) M12E7 Phase B 4 – 2 bolt mounting 76 (56) M12E8 Phase C 4 – 2 bolt mounting 76 (56) M12AC Output to Critical Load E9 Phase A 4 – 2 bolt mounting 76 (56) M12E10 Phase B 4 – 2 bolt mounting 76 (56) M12E11 Phase C 4 – 2 bolt mounting 76 (56) M12DC Input from Battery or BatteryDisconnect to UPS – CommonBatteryE4 Battery (+) 8 – 2 bolt mounting 76 (56) M12E5 Battery (-) 8 – 2 bolt mounting 76 (56) M12DC Input from Battery or BatteryDisconnect to UPS – SeparateBattery (UPM 1)E4 Battery (+) 4 – 2 bolt mounting 76 (56) M12E5 Battery (-) 4 – 2 bolt mounting 76 (56) M12DC Input from Battery or BatteryDisconnect to UPS – SeparateBattery (UPM 2)E4 Battery (+) 4 – 2 bolt mounting 76 (56) M12E5 Battery (-) 4 – 2 bolt mounting 76 (56) M12Input and Output Neutral E12 Neutral 8 – 2 bolt mounting 22 (16) M10Customer Ground Ground Ground 7 – 1 bolt mounting 22 (16) M10NOTE Customer ground, sized in accordance with NEC Table 250.122, can be run in any conduit listed in Table 3‐10.NOTE Bypass terminations are not applicable to IOM configurations.Table 3‐7. Supplied Intercabinet Wiring Terminal Hardware KitPart Size Quantity Terminals Used On Eaton Part NumberFlat Washer M8 36 UPM AC Input, UPM Battery Input, UPM ACOutput 180500036-080Conical Washer M8 36 UPM AC Input, UPM Battery Input, UPM ACOutput 180500037-080Nut M8 36 UPM AC Input, UPM Battery Input, UPM ACOutput 180200001-05