Figure 5 SCADA Terminal blockExtended control accessoryThe DC Motor Operator control can be operated viaa separate portable control when equipped with theappropriate accessory components. The Extended ControlAccessory components include the portable control, thecontrol cable, and modifications to the DC Control (ie: anadditional connector and associated wiring). The cable issupplied with a separable connector at both ends and canbe supplied in user-specified lengths up to 200 feet.otee:N Modifications to the DC Control should be made attime of manufacture, but can be purchased optionallyas a field retrofit kit.Figure 6 Extended control accessoryExtended control accessory operationThe DC Control can be optionally equipped with anaccessory which allows the control to be operated (in theLOCAL mode) from an additional portable control panel.Monitoring and operation are provided through the extendedcontrol accessory.941194KMControl operation – extended controlWith the DC Motor Operator Control SCADA toggle switchset to LOCAL and the rotary MOTOR SELECT switch setto the OFF position, the operation capabilities from theextended control accessory are:●● Select one of several motors.●● Read status of selected motor.●● Operate the selected motor.●● Monitor opening or closing action.●● Test indicating lights.The operation of each feature is described as follows:MOTOR SELECT SWITCH (ROTARY)e: Selects which motoris active for status indication and operation by the extendedlocal control. The SCADA switch must be set to theLOCAL position for extended local control operation.CLOSE (RED PUSH BUTTON)e: Closes the selected switchor interrupter mechanism, via the motor operator.OPEN (GREEN PUSH BUTTON)e: Opens the selectedswitch or interrupter mechanism, via the motor operator.STOP (YELLOW PUSH BUTTON)e: Stops the motor-operated opening or closing action of the selected switch orinterrupter mechanism.otee:N Mechanisms should not be left between an openor closed position. A mis-operation could occur.Restart the motor and actuate to a fully OPEN orfully CLOSED position.LAMP TEST (WHITE PUSH BUTTON)e: Checks statusindicator lights by energizing all lights.CLOSED INDICATION (RED LIGHT)e: Indicates thatthe selected switch or interrupter mechanism is in theclosed position.OPEN INDICATION (GREEN LIGHT)e: Indicates that theselected switch mechanism is in the open position. It alsoindicates that the fault interrupter mechanism is in eitherthe open or tripped position.CLOSING INDICATION (YELLOW LIGHT)e: Indicatesthat the motor actuator is closing the selected switch orinterrupter mechanism.OPENING INDICATION (YELLOW LIGHT)e: Indicatesthat the motor actuator is opening the selected switch orinterrupter mechanism.Important Notee: The VFI mechanism is a trip-freemechanism. If the VFI is closed by a motor operator anda fault occurs, the handle will be held in the CLOSEDposition, but the VFI mechanism will trip and the controlpanel will indicate OPEN. To reset the VFI, select the correctmotor and push the OPEN pushbutton. The motor operatorwill open and reset the VFI. The VFI can then be closed bypushing the CLOSE pushbutton.7OPERATION INSTRUCTIONS MN285018EN May 2017DC motor operator control installation and operation instructions