8Edison m o d u l a r f u s e ( E M F ) installation instru c t ionsINSTALLATION INSTRUCTIONS MN132031EN November 2016Adjustable foot bracket optionThe adjustable foot allows the base to be mounted atdifferent angles to the mounting structure. The adjustablefoot bracket is used with the standard channel base only.1. Assemble the adjustable bracket (Item 22) to the footbracket (Item 26) using 5/16-18 X 5/8” hex-head bolts,5/16” lock washers, and 5/16” nut (Items 23, 24, and25). Refer to Figure 27.Figure 27 Assembled adjustable foot bracketHex boltItem #23Adjustablebracket Item#22Foot bracketItem #26Nut Item#25Lock washerItem #24Figure 28 Adjustable foot bracket on standard channel baseChannelbase Item#1Adjustablebracket Item#222. Attach the adjustable bracket (Item 22) to the standardchannel base (Item 1) using 5/16-18 X 5/8” hex-headbolts, 5/16” lock washers, and 5/16” nut (Items 23,24, and 25). Attach the bracket to the side of the baseat the center hole and either the left or the right holeon the base. On the adjustable bracket, any of theholes along the perimeter can be used for positioningthe foot.) Refer to Figure 28.InstallationFigures 29 through 34 show typical installations of theEMF fuse. Figure 29 displays a typical horizontal installation;Figure 30 shows a typical vertical installation. Mount astypical installations or as specified by the utility.1. Attach the mounting assembly to the wall or othersupport structure.A. For the standard base, mount the assemblyusing the holes on the foot bracket, making surenecessary clearances are maintained. The brackethas provisions for 5/16” mounting hardware.otee:N Mounting hardware is not supplied with themounting assembly.B. For the top-hat base, mount the assembly usingthe mounting holes along the edge of the base,making sure necessary clearances are maintained.The mounting assembly has provisions for 1/2”mounting hardware.otee:N Mounting hardware is not supplied with themounting assembly.2. Install the 200 A dead-break or load-break inserts andelbows as specified by the manufacturer.3. The extended stand-off channel bracket can be rotatedby 90˚ increments to fit specified configuration: Loosenthe four mounting bolts that attach the bracket to thechannel base; reposition the bracket; and tighten themounting bolts.4. The standoff pockets can also be rotated to fit thespecified configuration: Loosen the mounting screw;rotate the pocket to the desired angle; and tighten thescrew.otee:N The mounting assembly can be grounded to thegrounding nut or as specified by the utility.