IF 1891 • 09/19 Copyright® 2019, Eaton’s Crouse-Hinds Division Page 3Figure 4WARNINGTo avoid ignition of the hazardous atmospheres or overheating of thefloodlight:Do not position the floodlight beyond the aiming range limits.3. Re-install back cover/heat sink and tighten all nine (9) mounting screws to 22 in.-lbs. (2.5 N-m). Be sure wires are not pinched during cover installation.• Replace any damaged or missing cover screws. Use only stainless steel#10-24 x 0.75”cover screws.4. To make final vertical adjustment, loosen the pivot bolts on the floodlight yoke toposition floodlight at the desired angle.5. Rotate the floodlight housing to the desired position.6. Tighten the two (2) pivot bolts to 45 ft.-lbs. (61 N-m).7. Turn power on.Input wire locationBGround Lug Location(Torque to 25 in.-lbs.)Mounting Screw(Torque to 19 in.-lbs.)Input wire locationGround lug location(torque to 25 in.-lbs.[2.82 N-m])Mountingscrew(torque to19 in.-lbs.[2.15 N-m])Figure 5EXTERNAL GROUND INSTALLATION INSTRUCTIONS1. Unscrew the ground lug fastener shown in Figure 5.2. Install stripped ground wire (0.5” [12.7mm]) in ground lug.3. Torque ground lug fastener down on ground wire. Torque to 25 in.-lbs. [2.82N-m], as shown in Figure 5.MAINTENANCE• Perform visual, electrical and mechanical inspections on a regular basis. Theenvironment and frequency of use should determine this. However, it isrecommended that checks be made at least once a year. We recommend anElectrical Preventive Maintenance Program as described in the National FireProtection Association Bulletin NFPA 70B: Recommended Practice for ElectricalEquipment Maintenance (www.nfpa.org).• The lens should be cleaned periodically to ensure continued lighting performance.To clean, wipe the lens with a clean, damp cloth. If this is not sufficient, use amild soap or a liquid cleaner such as Collinite NCF or Duco #7. Do not use anabrasive, strong alkaline or acid cleaner. Damage may result.• Visually check for undue heating evidenced by discoloration of wires or othercomponents, damaged parts or leakage evidenced by water or corrosion in theinterior. Replace all worn, damaged or malfunctioning components and cleangasket seals before putting the luminaire back into service.• Electrically check to make sure that all connections are clean and tight.• Mechanically check that all parts are properly assembled.• If the lens cover is removed from the fixture, the bezel gasket must be replaced tomaintain restricted breathing ratings.REPLACEMENT PARTSCrouse-Hinds Champ LED Floodlights are designed to provide years of reliable lightingperformance. However, should the need for replacement parts arise, they are availablethrough your authorized Crouse-Hinds distributor. Assistance may also be obtainedthrough your local Crouse-Hinds Sales Representative or the Crouse-Hinds SalesService Department, 1201 Wolf Street, Syracuse, New York 13208, Phone 866-764-5454.For replacement driver kits please see the following kit numbers, and theircorresponding applicable catalog numbers:• FMVA 3-5-7L UNV1 DRIVER KIT - covers FMVA/PFMA 3L, 5L and 7L UNV1luminaires• FMVA 9-11-13L UNV1 DRIVER KIT - covers FMVA/PFMA 9L, 11 and 13L UNV1luminaires• FMVA 15L UNV1 DRIVER KIT - covers FMVA/PFMA 15L UNV1 luminaires• FMVA 9L-11L UNV34 DRIVER KIT - covers FMVA/PFMA 9L, 11L UNV34 luminaires• FMVA 13L-15L UNV34 DRIVER KIT - covers FMVA/PFMA 13L and 15L UNV34luminaires60°45°105°VERTICALAIMING RANGE60° BEFOREVERTICAL45° PASTPIVOT1/2-13 BOLT5/16-18 ANGLE BOLTLOOSEN BOLTS TO SETFLOODLIGHT ANGLE