OPERATIONEATON Powerware® 9125 (9910-P30) UPS Installation Guide for IBM® Applications S 164201636 Rev A 37Configuration ModeWhen the UPS is in Configuration mode, the bar graph indicatorsrepresent the configuration options. Use the control buttons(On button and button) to modify the UPS configuration. Figure 39shows the LEDs and Table 16 explains the corresponding options.NOTE The UPS can be configured while in Battery mode. If the UPS transfers to batterypower while in Configuration mode, the UPS remains in Configuration mode and indicatesBattery mode on the front panel.1. Press the On button and the button simultaneously for onebeep. The UPS transfers to Configuration mode.The bar graph indicators flash briefly and then display the enabledoptions.2. Press the On button to scroll through the options. Each time youpress the button, the UPS beeps. The LED for the selected optionindicates the current setting; flashing represents disabled options(see Figure 39 and Table 16).If you press the On button and nothing happens, the UPS is still inOperation mode. Repeat Step 1 to enter Configuration mode, andthen perform Step 2.3. Press the button ONCE to toggle the selected option on or off.Repeat Steps 2 and 3 for each option. Scrolling past the last LEDreturns to the first configuration option.NOTE The UPS exits Configuration mode automatically after two minutes.4. Press the On button and the button simultaneously to exitConfiguration mode at any time.