POWER WIRING INSTALLATION NOTES011509D164201604-5 12 of 15DESCRIPTION:DATE:DRAWING NO: SHEET:REVISION:INSTALLATION INFORMATIONEaton 9390 UPS (100–160 kVA) Installation and Operation Manual 164201604 Rev E www.eaton.com/powerquality A-23Table O. INPUT/OUTPUT Ratings for 9390-120/100 and 9390-160/100 Parallel SystemsConfiguration Units Rating 50/60 HzBasic Unit Rating at 0.9 lagging pF load kVAkW1009010090100901009010090Input and Bypass InputOutputVOLTSVOLTS208/220208/220380380400400415415480480AllAC Input from UPMFull Load Current for each Module(3) Phases, (1) Neutral-if required, (1) Ground DAmps 278/262 152 144 139 120Minimum Conductor Size for each ModuleNumber per Phase for each ModuleAWG or kcmil(each)See Table E through Table G for wiresize.1+1AC Input to Tie Cabinet Bypass (optional)Full Load Current(3) Phases, (1) Neutral-if required, (1) GroundF Amps 278/262 152 144 139 120AC Output to Critical LoadFull Load Current(3) Phases, (1) Neutral-if required, (1) GroundG Amps 278/262 152 144 139 120System Neutral Bonding JumperMinimum Conductor SizeNumber (See Note 27)- AWG or kcmil(each)1/0(1)4(1)4(1)4(1)4(1)2+0and2+1AC Input to Tie Cabinet Bypass (optional)Full Load Current(3) Phases, (1) Neutral-if required, (1) GroundF Amps 556/524 304 288 278 240AC Output to Critical LoadFull Load Current(3) Phases, (1) Neutral-if required, (1) GroundG Amps 556/524 304 288 278 240System Neutral Bonding JumperMinimum Conductor SizeNumber (See Note 27)- AWG or kcmil(each)3/0(1)1/0(1)1/0(1)1/0(1)1/0(1)3+0and3+1AC Input to Tie Cabinet Bypass (optional)Full Load Current(3) Phases, (1) Neutral-if required, (1) GroundF Amps 834/786 456 432 417 360AC Output to Critical LoadFull Load Current(3) Phases, (1) Neutral-if required, (1) GroundG Amps 834/786 456 432 417 360System Neutral Bonding JumperMinimum Conductor SizeNumber (See Note 27)- AWG or kcmil(each)1/0(2)2/0(1)2/0(1)2/0(1)2/0(1)4+0AC Input to Tie Cabinet Bypass (optional)Full Load Current(3) Phases, (1) Neutral-if required, (1) GroundF Amps 1112/1048 608 576 556 480AC Output to Critical LoadFull Load Current(3) Phases, (1) Neutral-if required, (1) GroundG Amps 1112/1048 608 576 556 480System Neutral Bonding JumperMinimum Conductor SizeNumber (See Note 27)- AWG or kcmil(each)2/0(2)2/0(1)2/0(1)2/0(1)2/0(1)NOTE: Callout letters D, F, and G map to Drawing 164201604-4, sheets 4 of 6, 5 of 6,and 6 of 6.