POWERWARE SYNC CONTROL INSTALLATIONEATON Powerware® 9390 and 9395 Sync Control Installation and Operation Manual 164201571 Rev E www.powerware.com 3−73.2 Installation and Wiring with a Powerware 9395 UPSNOTE When installing wiring connections, conduit must be installed between the Powerware Sync Control andthe UPS cabinet. Conduit also must be installed between the Powerware Sync Control and the customer’s remotemonitoring system.To install and wire:1. Install the Powerware Sync Control panel to the selected mounting location.See Figure 2-1 on page 2−2 for mounting hole dimensions and Figure 2-2 onpage 2−3 for conduit entrance locations.2. Unfasten the front door latches and swing the door open.3. Complete all control wiring interconnections using Table 3-3 for wiringrequirements.Figure 3-1 on page 3−3 shows the Powerware Sync Control TB1 terminal blockand ground terminal locations. Figure 3-2 on page 3−4 shows the TB1 terminalblock wiring detail.Figure 3-6 through Figure 3-9 starting on page 3−9 show the typical locations ofthe UPS TB3, TB6, and X−Slot® Relay Interface Card interconnect terminal blocks.Figure 3-5 on page 3−6 shows the TB6 detail.Refer to the applicable Powerware 9395 UPS Installation and Operation Manuallisted in paragraph 1.3 on page 1−4 for UPS cabinet terminal locations andassignments, termination requirements, conduit landing locations, and terminalaccess instructions.NOTE Complete the wiring to the X−Slot Relay Interface Card terminals before installing the cards in theCommunication Bay in each of the UPS cabinets.4. Route wires through the strain relief bushing and connect to the terminals on theX−Slot Relay Interface Card in each of the UPS cabinets (see Figure 3-10 onpage 3−13 and Figure 3-11 on page 3−13).5. Install the X−Slot Relay Interface Card into an open X−Slot communication bay onthe front of the UPS (see Figure 3-6 on page 3−9, Figure 3-7 on page 3−10,Figure 3-8 on page 3−11, or Figure 3-9 on page 3−12). Refer to the applicablePowerware 9395 UPS Installation and Operation Manual listed in paragraph 1.3on page 1−4 for UPS cabinet access instructions.6. Verify the jumper is installed between Sync Control terminal TB1−40 and TB1−41(see Figure 3-2 on page 3−4).7. If applicable, complete all customer remote monitoring system wiringinterconnections using Table 3-2 on page 3−3 for wiring requirements.Figure 3-2 on page 3−4 shows the TB1 terminal block wiring detail.8. When all wiring is complete, close the door and secure the latch.C A U T I O NWhen connecting the bypass and load voltage from another model UPS to a Powerware 9395 UPS using thePowerware Sync Control accessory, use Phase A, Phase B, and Neutral connections from the other UPS. DO NOTconnect the other model UPS Phase C bypass and load voltage to the Sync Control connection point whenconnecting to a Powerware 9395 UPS.