POWER WIRING INSTALLATION NOTES032406B164201604---5 3 of 15DESCRIPTION:DATE:DRAWING NO: SHEET:REVISION:Installation InformationA-14 EATON Powerware® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.comTable G. INPUT/OUTPUT Ratings & External Wiring Requirements for the Powerware9390---160/160Units Rating 50/60 HzBasic Unit Rating at 0.9 lagging pF load kVAkW160144160144Input and Bypass InputOutputVOLTSVOLTS208/220208/220480480AC Input to UPS Rectifier (0.98 min. pF)Full Load Current plus Battery Recharge Current(3) Phases, (1) Ground AAmps 480 210Minimum Conductor SizeNumber per PhaseAWG or kcmil(each)400(2)1/0(2)AC Input to UPS BypassFull Load Current(3) Phases, (1) Neutral---if required, (1) Ground BAmps 444/420 192Minimum Conductor SizeNumber per PhaseAWG or kcmil(each)400(2)1/0(2)DC Input from Battery to UPS(1) Positive, (1) NegativeCVdcAmps@ (2.0V/cell)384---480403432---480403Minimum Conductor SizeNumber per PoleAWG or kcmil(each)250(2)250(2)AC Output to Critical LoadFull Load Current(3) Phases, (1) Neutral---if required, (1) Ground D Amps 444/420 192Minimum Conductor SizeNumber per PhaseAWG or kcmil(each)400(2)1/0(2)Neutral Bonding JumperMinimum Conductor SizeNumber (See Note 7) --- AWG or kcmil(each)1/0(2)2(2)NOTE: Callout letters A, B, C, and D map to Drawing 164201604 ---4, sheets 1 of 6,2 of 6, 4 of 6, 5 of 6, and 6 of 6.C A U T I O NDELTA SOURCES (TN-S) - The Powerware 9390 UPS system can be operated only from a deltasupply source that is fully floating and if the neutral-forming transformer kit (PN 103005400) isinstalled in the UPS. The UPS cannot be operated from a mid-point or end-point groundeddelta supply source. With this type of supply source, there is no capability to provide an outputneutral. In no circumstances shall a neutral to ground bonding jumper be installed in the UPS.8. The UPS cabinet is shipped with a debris shield covering the ventilation grill on top of theunit. Do not remove the debris shield until installation is complete. However, remove theshield before operating the UPS. Once the debris shield is removed, do not place objectson the ventilation grill.9. Refer to Section I of this manual for installation instructions.