POWER WIRING INSTALLATION NOTES032406B164201604---5 13 of 15DESCRIPTION:DATE:DRAWING NO: SHEET:REVISION:Installation InformationA-24 EATON Powerware® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.comTable P. INPUT/OUTPUT Ratings for Powerware 9390---120/120 and 9390---160/120 Parallel SystemsConfiguration Units Rating 50/60 HzBasic Unit Rating at 0.9 lagging pF load kVAkW120108120108Input and Bypass InputOutputVOLTSVOLTS208/220208/220480480AllAC Input from UPMFull Load Current for each Module(3) Phases, (1) Neutral---if required, (1) Ground DAmps 333/315 144Minimum Conductor Size for each ModuleNumber per Phase for each ModuleAWG or kcmil(each)See Table E throughTable G for wire size.1+1AC Input to Tie Cabinet Bypass (optional)Full Load Current(3) Phases, (1) Neutral---if required, (1) GroundF Amps 333/315 144AC Output to Critical LoadFull Load Current(3) Phases, (1) Neutral---if required, (1) GroundG Amps 333/315 144System Neutral Bonding JumperMinimum Conductor SizeNumber (See Note 27)--- AWG or kcmil(each)1/0(1)4(1)2+0and2+1AC Input to Tie Cabinet Bypass (optional)Full Load Current(3) Phases, (1) Neutral---if required, (1) GroundF Amps 666/630 288AC Output to Critical LoadFull Load Current(3) Phases, (1) Neutral---if required, (1) GroundG Amps 666/630 288System Neutral Bonding JumperMinimum Conductor SizeNumber (See Note 27)--- AWG or kcmil(each)3/0(1)1/0(1)3+0and3+1AC Input to Tie Cabinet Bypass (optional)Full Load Current(3) Phases, (1) Neutral---if required, (1) GroundF Amps 999/945 432AC Output to Critical LoadFull Load Current(3) Phases, (1) Neutral---if required, (1) GroundG Amps 999/945 432System Neutral Bonding JumperMinimum Conductor SizeNumber (See Note 27)--- AWG or kcmil(each)1/0(2)2/0(1)4+0AC Input to Tie Cabinet Bypass (optional)Full Load Current(3) Phases, (1) Neutral---if required, (1) GroundF Amps 1332/1260 576AC Output to Critical LoadFull Load Current(3) Phases, (1) Neutral---if required, (1) GroundG Amps 1332/1260 576System Neutral Bonding JumperMinimum Conductor SizeNumber (See Note 27)--- AWG or kcmil(each)2/0(2)2/0(1)NOTE: Callout letters D, F, and G map to Drawing 164201604 ---4, sheets 4 of 6, 5 of 6,and 6 of 6.