UPS OPERATING INSTRUCTIONSEaton 9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual 164201710 Rev 2 www.eaton.com\powerquality7-107.2.8 System Status Screen and ControlsPress the CONTROLS pushbutton on the main menu bar to display the System Statusscreen. Online operation, transfer to bypass, charger control, UPM startup andshutdown, and LOAD OFF commands are controlled through this screen. In addition,the screen displays the current status of the UPS, indicates whether the UPS is inMaintenance Bypass or Bypass, and displays the state of the UPM and batterycharger. Figure 7‐6 shows the System Status screen.Use the or pushbutton on the System Status menu bar to highlight thecommand screen desired, then press the CONTROLS pushbutton to display thecommand menu screen.Table 7‐4 lists the typical System Status Screen Messages that are displayed duringUPS operation.Table 7‐5 describes the control functions and provides instructions to access and usethe command menu screens.For detailed information about using the System Controls, see paragraph 7.3.MAINTENANCE BYPASSBYPASSUPM: OFFLINESHUTDOWN: AVAILABLE:OFF:SYSTEM STATUSCONTROLSESCCHARGER OFF:UPSFigure 7‐6. Typical System Status ScreenTable 7‐4. Typical System Status MessagesFunction MessageUPS Shutdown; Bypass; Online; Online with ESS;Online +VMMS; High AlertBypass Off; On; AvailableMaintenance Bypass Off; OnCharger Charger Off; ChargingUPM (during startup) DC Starting, Charger Off; DC Starting, Close BatteryBreaker; Inverter Starting; Inverter Syncing; Ready; OnlineUPM 1UPM 2Offline; Shutdown, Charger Off; Ready; Ready, Charging;Online, Charger Off; Online, Charging