UPS OPERATING INSTRUCTIONSEaton 9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual 164201710 Rev 2 www.eaton.com\powerquality 7-418. To turn off the power module, press the CONTROLS pushbutton on the UPSControl Command menu bar. The UPM 1 Control Command screen is displayed.9. On the UPM 1 Control Command screen, select UPM OFF.10. Press the SELECT pushbutton on the UPM 1 Command menu bar.The UPM status indicates SHUTDOWN. The power module is turned off.Logic power remains on.11. Repeat Steps 4 through 10 selecting UPM 2 to shut down UPM 2.12. Repeat Steps 2 through 11 for each UPS in the distributed bypass system.W A R N I N GPower is present inside the UPS cabinet.7.4.20 Single UPM ShutdownTo shut down a single UPM:1. Press the CONTROLS pushbutton on the main menu bar. The System Statusscreen is displayed.2. On the System Status screen, select the UPM Command. The UPS ControlCommand screen is displayed.3. On the UPS Control Command screen, select the UPM to shut down.4. Press the CONTROLS pushbutton on the UPS Control Command menu bar. TheUPM Control Command screen is displayed.5. On the UPM Control Command screen, select UPM OFF.6. Press the SELECT pushbutton on the UPM Command menu bar.The UPM status indicates READY. The input, output, and battery contactorsopen, and the power module remains on. The remaining UPMs supply thecritical load.7. To turn off the power module, press the CONTROLS pushbutton on the UPSControl Command menu bar. The UPM Control Command screen is displayed.8. On the UPM Control Command screen, select UPM OFF.9. Press the SELECT pushbutton on the UPM Command menu bar.The UPM status indicates SHUTDOWN. The power module is turned off. Theremaining UPMs continue to supply the critical load.Logic power remains on.