Setup and Starting—Initial Configuration6 S611 Soft Starter MN03901003E—January 2012 www.eaton.comSetup and Starting—Initial Configuration1. The S611 Operation and Protection parameters may beedited when 120 Vac control power is applied to 120 Vacsupply (TB1). Mains power is not required to edit andsave Operation and/or Protection parameters.2. If any 120 Vac power source other than the normal systemcontrol power source is used to power the control circuit toedit parameters, connections must be made in compliancewith all local, state, and national electrical codes.3. To setup the S611 Operating parameters (Operationmode), perform the following steps:a. Enter motor FLA.b. Enter motor rated voltage.c. Select start method if required (default = voltageramp, or pump start).d. Enter Start time from table on Page 7 (default =20 seconds).e. Enter initial torque from table on Page 7 (default =45%).f. Enter Stop time, Kick Start time, and Kick Starttorque if desired (default = 0).4. Application NotesAdjust Initial Torque for smooth start, motor rotationshould begin within 2 seconds.If Stall Faults occur at the end of the ramp time, increaseInitial Torque, Kick Start Torque and Time and/or SoftStart Time to achieve bypass before the Soft Start timeelapses. Verify that the motor is not overloaded.After suitable performance has been achieved with eithermethod, determine the starting time to bypass and setSoft Start Time at 1.25 times this time. For example, if ittakes 10 seconds to accelerate the motor and go intobypass, set the Soft Start Time for 12.5 seconds.5. In the Protection Mode, set the Protection parametersto the desired values. Refer to table on Page 7.6. For optional advanced configuration parameters refer tothe user manual.Operating ParametersNotes For the device with pump option, the default value is 2 for pump start.Operating Parameter Units Min Max Default NotesMotor FLA Amps Motor FLA parameter must be set tomotor nameplate FLA to achieveproper overload protectionFrame Size A–52 26 52 26Frame Size A–65 32.5 65 32.5Frame Size A–77 38.5 77 38.5Frame Size B–99 48 99 48Frame Size B–125 62.5 125 62.5Frame Size C–156 78 156 78Frame Size C–180 90 180 90Frame Size D–242 120 242 120Frame Size E–302 151 302 151Frame Size E–361 180.5 361 180.5Frame Size F–414 207 414 207Motor rated voltage Volts 200 600 480 —Start method — 0 2 0 0 = Voltage ramp1 = Current limit2 = Pump start (option)Start time Seconds 0.5 180 20 —Initial torque % 0 100 45 —Stop time Seconds 0 60 0 —Kick start time Seconds 0 2 0 —Kick start torque % 0 100 0 —Auto reset mode — 0 1 0 0 = Manual1 = AutoAdvanced config — — — — Refer to User Manual, Publication No.MN03902011Ewww.comoso.com