Installation2 S611 Soft Starter MN03901003E—January 2012 www.eaton.comCT Polarity Identification CT LocationLine and Load Power Wiring Notes Additional lug selection may be found in Appendix D of the User Manual, Publication No. MN03902011E. Each lug kit consists of three lugs. Two kits are required for both line and load connections. Wire size based on 125% of UL 508 Table 43.2.Short-Circuit RatingSuitable for use on a circuit capable of delivering not more than 100,000 rmssymmetrical amperes, 600 volts maximum when protected by Class RK5 fuses or acircuit breaker having an interrupting rating not less than 65,000 rms symmetricalamperes, 480 volts maximum.CurrentRatingConductorSize Number ofConductorsMechanical Lug—Ilsco Part NumberTorquelb-inMechanicalLug RangeSoft StarterCatalog NumberMechanical Lug—Eaton Catalog Number52A 6 AWG 1 TA-2/0 120 14 AWG–2/0 S611A052XXX S611-LUG-MO165A 4 AWG 1 TA-2/0 120 14 AWG–2/0 S611A065XXX S611-LUG-MO177A 3 AWG 1 TA-2/0 120 14 AWG–2/0 S611A072XXX S611-LUG-MO199A 1/0 AWG 1 TA-300 275 14 AWG–2/0 S611B099XXX S611-LUG-MO2125A 2/0 AWG 1 TA-300 275 2 AWG–600 kcmil S611B125XXX S611-LUG-MO2156A 3/0 AWG 1 TA-600 500 2 AWG–600 kcmil S611C156XXX S611-LUG-MO3180A 4/0 AWG 1 TA-600 500 2 AWG–600 kcmil S611C180XXX S611-LUG-MO3242A 350 kcmil 1 TA-600 500 2 AWG–600 kcmil S611D242XXX S611-LUG-MO3302A 3/0 AWG 2 AU-600-2NS 500 2 AWG–600 kcmil S611E302XXX S611-LUG-MO4361A 4/0 AWG 2 AU-600-2NS 500 2 AWG–600 kcmil S611E361XXX S611-LUG-MO4414A 300 kcmil 2 AU-600-2NS 500 300–800 kcmil S611F414XXX S611-LUG-MO4www.comoso.com