June 200666For more information visit: www.EatonElectrical.com CA04000006ESVX9000 Adjustable Frequency DrivesVFD Pump PanelsTechnical Data and SpecificationsTable 96. Specifications Some horsepower units include dynamic braking chopper asstandard — refer to individual drive sections.Table 97. Standard I/O SpecificationsFeature Description 9000X Enclosed Products —NEMA Type 12 or NEMA Type 3RPrimary Design Features45 – 66 Hz Input Frequency StandardOutput: AC Volts Maximum Input Voltage BaseOutput Frequency Range: Hz 0 – 320Initial Output Current (IH) 250% for 2 secondsOverload: 1 Minute (IH/IL) 150%/110%Enclosure Space Heater OptionalOversize Enclosure StandardOutput Contactor OptionalBypass Motor Starter OptionalListings UL, cULProtection FeaturesIncoming Line Fuses OptionalAC Input Circuit Disconnect OptionalLine Reactors StandardPhase Rotation Insensitive StandardEMI Filter Standard — Thru Frame 9Input Phase Loss Protection StandardInput Overvoltage Protection StandardLine Surge Protection StandardOutput Short Circuit Protection StandardOutput Ground Fault Protection StandardOutput Phase Protection StandardOvertemperature Protection StandardDC Overvoltage Protection StandardDrive Overload Protection StandardMotor Overload Protection StandardProgrammer Software OptionalLocal/Remote Keypad StandardKeypad Lockout StandardFault Alarm Output StandardBuilt-In Diagnostics StandardInput/Output Interface FeaturesSetup Adjustment Provisions:Remote Keypad/DisplayPersonal ComputerStandardStandardOperator Control Provisions:Drive Mounted Keypad/DisplayRemote Keypad/DisplayConventional Control ElementsSerial Communications115V AC Control CircuitStandardStandardStandardOptionalOptionalSpeed Setting Inputs:Keypad0 – 10V DC Potentiometer/Voltage Signal4 – 20 mA Isolated4 – 20 mA DifferentialStandardStandardConfigurableConfigurableAnalog Outputs:Speed/FrequencyTorque/Load/CurrentMotor VoltageKilowatts0 – 10V DC Signals4 – 20 mA DC SignalsIsolated SignalsStandardProgrammableProgrammableProgrammableConfigurable w/JumpersStandardOptionalFeature Description 9000X Enclosed Products —NEMA Type 12 or NEMA Type 3RInput/Output Interface Features (Continued)Discrete Outputs:Fault AlarmDrive RunningDrive at Set SpeedOptional ParametersDry ContactsOpen Collector OutputsAdditional Discrete OutputsStandardStandardProgrammable141 (2 Relays Form C)1OptionalCommunications:RS-232RS-422/485DeviceNet™Modbus RTUCanOpen (Slave)Profibus-DPLonworks®Johnson Controls Metasys™ N2StandardOptionalOptionalOptionalOptionalOptionalOptionalOptionalPerformance FeaturesSensorless Vector Control StandardVolts/Hertz Control StandardIR and Slip Compensation StandardElectronic Reversing StandardDynamic Braking Optional DC Braking StandardPID Setpoint Controller ProgrammableCritical Speed Lockout StandardCurrent (Torque) Limit StandardAdjustable Acceleration/Deceleration StandardLinear or S Curve Accel/Decel StandardJog at Preset Speed StandardThread/Preset Speeds 7Automatic Restart SelectableCoasting Motor Start StandardCoast or Ramp Stop Selection StandardElapsed Time Meter OptionalCarrier Frequency Adjustment 1 – 16 kHzStandard Conditions for Application and ServiceOperating Ambient Temperature 0 – 40°CStorage Temperature -40 – 60°CHumidity (Maximum),Non-condensing95%Altitude (Maximum without Derate) 3300 ft. (1000m)Line Voltage Variation +10/-15%Line Frequency Variation 45 – 66 HzEfficiency >96%Power Factor (Displacement) .96Description Specification6 – Digital Input Programmable 24V: “0” ) 10V, “1” * 18V,Ri > 5 k2 – Analog Input Configurablew/JumpersVoltage: 0 – ±10V, Ri > 200 kCurrent: 0 (4) – 20 mA, Ri = 250 k2 – Digital Output Programmable Form C Relays 250V AC 2 Amp or30V DC2 Amp resistive1 – Digital Output Programmable Open collector 48V DC 50 mA1 – Analog Output ProgrammableConfigurable w/Jumper0 – 20 mA, impedance 500 ohms,resolution 106 ±3%