POWER WIRING INSTALLATION NOTES092107DESCRIPTION:DATE:DRAWING NO: SHEET:REVISION: E164201546---4 7 of 10INSTALLATION INFORMATIONEATON Powerware® 9390 UPS Sidecar Installation and Operation Manual S 164201586 Rev E www.powerware.com A-23Table K. UPS Sidecar 1+1 Parallel Redundant Power Cable Terminations120/100, 120/120 kVA 480/480VTerminal Function FunctionSize of PressureTerminationTightening TorqueNm (lb in)TypeScrewAC Input from UPM2 toMOB 2 (standaloneinstallation)Phase A 1 --- #4---350 kcmil 20.3 (180) 3/16” HexPhase B 1 --- #4---350 kcmil 20.3 (180) 3/16” HexPhase C 1 --- #4---350 kcmil 20.3 (180) 3/16” HexAC Output to Critical Load(without SLB)Phase A 1 --- #6---500 kcmil 56.5 (500) 1/2 HexPhase B 1 --- #6---500 kcmil 56.5 (500) 1/2 HexPhase C 1 --- #6---500 kcmil 56.5 (500) 1/2 HexAC Output to Critical Load(with SLB)Phase A 1 --- #4---350 kcmil 20.3 (180) 3/16” HexPhase B 1 --- #4---350 kcmil 20.3 (180) 3/16” HexPhase C 1 --- #4---350 kcmil 20.3 (180) 3/16” HexNeutral Neutral 8 --- #6---250 kcmil 42.4 (375) 5/16” HexGround Ground 4 --- #14---1/0 5.6 (50) SlottedTable L. UPS Sidecar 1+1 Parallel Redundant Power Cable Terminations80/40, 80/50, 80/60, 80/80 kVA 208/208VTerminal Function FunctionSize of PressureTerminationTightening TorqueNm (lb in)TypeScrewAC Input from UPM2 toMOB 2 (standaloneinstallation)Phase A 1 --- 2/0---250 kcmil1 --- 2/0---500 kcmil31.1 (275)31.1 (275)5/16” Hex3/8” HexPhase B 1 --- 2/0---250 kcmil1 --- 2/0---500 kcmil31.1 (275)31.1 (275)5/16” Hex3/8” HexPhase C 1 --- 2/0---250 kcmil1 --- 2/0---500 kcmil31.1 (275)31.1 (275)5/16” Hex3/8” HexAC Output to Critical Load(without SLB) Phase A 1 --- 2/0---250 kcmil1 --- 2/0---500 kcmil31.1 (275)31.1 (275)5/16” Hex3/8” HexPhase B 1 --- 2/0---250 kcmil1 --- 2/0---500 kcmil31.1 (275)31.1 (275)5/16” Hex3/8” HexPhase C 1 --- 2/0---250 kcmil1 --- 2/0---500 kcmil31.1 (275)31.1 (275)5/16” Hex3/8” HexAC Output to Critical Load(with SLB) Phase A 1 --- 2/0---250 kcmil1 --- 2/0---500 kcmil31.1 (275)31.1 (275)5/16” Hex3/8” HexPhase B 1 --- 2/0---250 kcmil1 --- 2/0---500 kcmil31.1 (275)31.1 (275)5/16” Hex3/8” HexPhase C 1 --- 2/0---250 kcmil1 --- 2/0---500 kcmil31.1 (275)31.1 (275)5/16” Hex3/8” HexNeutral Neutral 8 --- #6---250 kcmil 42.4 (375) 5/16” HexGround Ground 4 --- #14---1/0 5.6 (50) Slotted13. Conduit is to be sized to accommodate one neutral conductor the same size as the phaseconductor and one #8 AWG ground conductor. If two neutral conductors or an oversizedneutral conductor are to be installed, size the conduit to accommodate the extra wire orsize. All Powerware 9390 products can accommodate a double-sized neutral.14. External UPS Sidecar rectifier and bypass input overcurrent protection is not provided bythis product, but is required by codes. Refer to Table B through Table E for wiringrequirements.