TroubleshootingEaton ePDU G3 Troubleshooting Guide P-164000278—Rev 1 www.eaton.com/ePDU 192 215200 Eaton ePDU Input 2 Low Voltage Critical The specified section voltage reading is less than thevalue configured as the low voltage critical threshold.2 215300 Eaton ePDU Input 2 High Voltage Warning The specified section voltage reading is greater thanthe value configured as the over voltage warningthreshold.2 215400 Eaton ePDU Input 2 High Voltage Critical The specified section voltage reading is greater thanthe value configured as the over voltage criticalthreshold.2 216000 Eaton ePDU Input 2 Frequency OK The frequency is not out of range.2 216100 Eaton ePDU Input 2 Frequency out of +/- 3 HztoleranceThe frequency is out of range.2 221000 Eaton ePDU Gang Phase Input Current NoThresholdNo section current threshold has been triggered.2 221100 Eaton ePDU Gang Phase Low CurrentWarningThe current amperage (A) reading for the specifiedsection is less than the value configured as the lowcurrent warning alarm threshold.2 221200 Eaton ePDU Gang Phase Low Current Critical The current amperage (A) reading for the specifiedsection is less than the value configured as the lowcurrent critical alarm threshold.2 221300 Eaton ePDU Gang Phase Over CurrentWarningThe specified section current amperage (A) reading isgreater than the value configured as the over currentwarning threshold.2 221400 Eaton ePDU Gang Phase Over Current Critical The specified section input current amperage (A)reading is greater than the value configured as theover current critical alarm threshold.2 222000 Eaton ePDU Gang Phase Voltage NoThresholdNo section voltage threshold has been triggered.2 222100 Eaton ePDU Gang Phase Low VoltageWarningThe specified section voltage reading is less than thevalue configured as the low voltage warningthreshold.2 222200 Eaton ePDU Gang Phase Low Voltage Critical The specified section voltage reading is less than thevalue configured as the low voltage critical threshold.2 222300 Eaton ePDU Gang Phase Over VoltageWarningThe specified section voltage reading is less than thevalue configured as the over voltage warningthreshold.2 222400 Eaton ePDU Gang Phase Over Voltage Critical The specified section voltage reading is less than thevalue configured as the over voltage criticalthreshold.2 223000 Eaton ePDU Gang Breaker Reset No alarm has been triggered.2 223100 Eaton ePDU Gang Breaker Tripped An alarm has been triggered.2 241000 Communication OK No communication failure detected on TeridianRS-485 bus2 241100 Communication Lost Communication failure detected on Teridian RS-485bus2 251000 Daisy Chain Communication OK No communication failure detected on Daisy Chain2 251100 Daisy Chain Communication Alarmed Communication failure detected on Daisy Chain2 231000 Eaton ePDU Outlet Current No Threshold No outlet current threshold has been triggered.Table 11. ePDU and User Alarms and Events (Continued)Type CodeIdentification andIndex Code Alarm or Event Description