Eaton - Lighting Systems iLight Product Series - UIG-2 73-898-00 IM8840 Iss.02 4Outputs4 LED OutputsA. LED outputs drive remote indicatorsB. Each output provides a 10mA supplycapable of driving LED’s up to a forward dropof 6.7V.C. Indicates input status when opto-isolatedinput are configured for scene selectionD. Can also be configured for indication ofother functionsE. All LED outputs wire with 2 part connectorswith screw terminals. Wire sizes 4mm2 (12AWG) to 0.25mm2 (24 AWG).FunctionsA. 16 sequences of up to 128 steps eachB. 4 room joins with up to 3 partitions eachAmbient atmosphere requirementsTemperature: 0°C to +40°C (32°F to 104°F)Humidity: 0 to 95% non-condensing.Electrical and networkA. Supply: 12Vdc from the iCANnet network.B. Counts as 1 device load when used with 4LED outputs or with 1 sensor.C. Every additional 2 sensors increases thesupply load by 1 device.D. Will operate from 12Vdc to 18Vdc.E. iCANnet network connection: 2 partconnector with screw terminals. Wire sizesfrom 4mm2 (12AWG) – 0.25mm2 (24AWG).F. Maximum wiring distance of inputs shouldnot exceed 10m (32 feet).InstallationSupplied PartsThe universal interface is supplied with amounting plate for easy attachment to astandard double gang UK style electrical backbox (not included).MountingThe mounting plate can be removed if it isnot required, allowing the universal interfaceto be mounted in any convenient location. Ifdoing so, you must ensure that the universalinterface is supported such that it is electricallyisolated from any electrically conductivematerial in that location. The unit must beinstalled in a dry,ventilated location where ambient temperatureand humidity are within the operating limits ofthe product.