PLT-22 Transceiver Isolation Transformer Schematic1234Primary SecondaryPLT-22 Transceiver Isolation Transformer ElectricalSpecificationsBelow are specifications for the PLT-22 Transceiver Isolation Transformer Schematicshown above.Parameter Min Typ Max UnitsTurns Ratio (1-2) : (3-4) 1.0DC Resistance1-23-40.200.20OhmOhmMagnetizing Inductance 1-2Dry, @100kHz, 1Vrms0.75 1.0 1.25 mHMagnetizing Inductance 1-2,Wet, @100kHz, 1Vrms,plus15mADC0.75 mHLeakage Inductance 1-2(3-4 shorted) @100kHz, 1Vrms10.8 12.0 13.2 μHWinding Capacitance 1-2 30 pFWinding to Winding Capacitance1-2 shorted to 3-4 shorted30 pFA-2 Appendix A