GE Multilin B30 Bus Differential System 6-196 ACTUAL VALUES 6.4 RECORDS66.4RECORDS 6.4.1 USER-PROGRAMMABLE FAULT REPORTSPATH: ACTUAL VALUES RECORDS USER-PROGRAMMABLE FAULT REPORTThis menu displays the user-programmable fault report actual values. See the User-Programmable Fault Report section inchapter 5 for additional information on this feature.6.4.2 EVENT RECORDSPATH: ACTUAL VALUES RECORDS EVENT RECORDSThe event records menu shows the contextual data associated with up to the last 1024 events, listed in chronological orderfrom most recent to oldest. If all 1024 event records have been filled, the oldest record will be removed as a new record isadded. Each event record shows the event identifier/sequence number, cause, and date/time stamp associated with theevent trigger. See the COMMANDS CLEAR RECORDS menu for clearing event records.Only major output operands generate events, not every operand. Elements that assert output per phase, for example, logoperating phase output only without asserting the common three-phase operand event.6.4.3 OSCILLOGRAPHYPATH: ACTUAL VALUES RECORDS OSCILLOGRAPHYThis menu allows the user to view the number of triggers involved and number of oscillography traces available. TheCYCLES PER RECORD value is calculated to account for the fixed amount of data storage for oscillography. See the Oscillog-raphy section of chapter 5 for additional details. USER-PROGRAMMABLE FAULT REPORTNEWEST RECORDNUMBER: 0MESSAGE LAST CLEARED DATE:2002/8/11 14:23:57MESSAGE LAST REPORT DATE:2002/10/09 08:25:27 EVENT RECORDSEVENT: XXXXRESET OP(PUSHBUTTON)↓MESSAGE EVENT: 3POWER ONEVENT 3DATE: 2000/07/14MESSAGE EVENT: 2POWER OFFEVENT 3TIME: 14:53:00.03405MESSAGE EVENT: 1EVENTS CLEARED Date and Time Stamps OSCILLOGRAPHYFORCE TRIGGER?NoRange: No, YesMESSAGE NUMBER OF TRIGGERS:0MESSAGE AVAILABLE RECORDS:0MESSAGE CYCLES PER RECORD:0.0MESSAGE LAST CLEARED DATE:2000/07/14 15:40:16