GE Multilin B30 Bus Differential System 10-110 MAINTENANCE 10.1 MODULES1010 MAINTENANCE 10.1 MODULES 10.1.1 REPLACE A MODULEWithdraw or insert a module only when control power has been removed from the unit, and besure to insert only the correct module type into a slot, else personal injury, damage to the unitor connected equipment, or undesired operation can result.To avoid damage to the equipment, use proper electrostatic discharge protection (for example, astatic strap) when coming in contact with modules while the relay is energized.The relay, being modular in design, allows for the withdrawal and insertion of modules. Modules must only be replaced withlike modules in their original factory configured slots.The enhanced faceplate can be opened to the left, once the thumb screw has been removed, as shown below. This allowsfor easy accessibility of the modules for withdrawal. The new wide-angle hinge assembly in the enhanced front panel openscompletely and allows easy access to all modules in the B30.Figure 10–1: UR MODULE WITHDRAWAL AND INSERTION (ENHANCED FACEPLATE)The standard faceplate can be opened to the left, once the sliding latch on the right side has been pushed up, as shownbelow. This allows for easy accessibility of the modules for withdrawal.Figure 10–2: UR MODULE WITHDRAWAL AND INSERTION (STANDARD FACEPLATE)To properly remove a module, the ejector/inserter clips, located at the top and bottom of each module, must be pulledsimultaneously. Before performing this action, control power must be removed from the relay. Record the original loca-tion of the module to ensure that the same or replacement module is inserted into the correct slot. Modules with currentinput provide automatic shorting of external CT circuits.WARNINGNOTICE842812A1.CDR