GE Multilin B90 Low Impedance Bus Differential System 6-56 ACTUAL VALUES 6.2 STATUS66.2.7 REMOTE DEVICESa) STATUSPATH: ACTUAL VALUES STATUS REMOTE DEVICES STATUSThe present state of the programmed remote devices is shown here. The ALL REMOTE DEVICES ONLINE message indicateswhether or not all programmed remote devices are online. If the corresponding state is "No", then at least one requiredremote device is not online.b) STATISTICSPATH: ACTUAL VALUES STATUS REMOTE DEVICES STATISTICS REMOTE DEVICE 1(16)Statistical data (two types) for up to 16 programmed remote devices is shown here.The StNum number is obtained from the indicated remote device and is incremented whenever a change of state of atleast one DNA or UserSt bit occurs. The SqNum number is obtained from the indicated remote device and is incrementedwhenever a GSSE message is sent. This number will rollover to zero when a count of 4 294 967 295 is incremented.6.2.8 FLEX STATESPATH: ACTUAL VALUES STATUS FLEX STATESThere are 256 FlexState TM bits available. The second line value indicates the state of the given FlexState bit. REMOTE DEVICES STATUSAll REMOTE DEVICESONLINE: NoRange: Yes, NoMESSAGE REMOTE DEVICE 1STATUS: OfflineRange: Online, OfflineMESSAGE REMOTE DEVICE 2STATUS: OfflineRange: Online, OfflineMESSAGE REMOTE DEVICE 16STATUS: OfflineRange: Online, Offline REMOTE DEVICE 1REMOTE DEVICE 1StNum: 0MESSAGE REMOTE DEVICE 1SqNum: 0 FLEX STATESPARAM 1: OffOffRange: Off, OnMESSAGE PARAM 2: OffOffRange: Off, OnMESSAGE PARAM 256: OffOffRange: Off, On