5-288 D60 Line Distance Protection System GE Multilin5.7 CONTROL ELEMENTS 5 SETTINGS5elements, breaker failure, and close and trip commands. A six-cycle time delay applies after the selected FlexLogicoperand resets.• BRK FLSHOVR PKP DELAY: This setting specifies the time delay to operate after a pickup condition is detected.Figure 5–154: BREAKER FLASHOVER SCHEME LOGIC842018A2.CDRANDANDANDSETdominantRESETSETdominantRESETORORORORORBREAKER FLASHOVERFUNCTION: BRK 1 FLSHOVR V PKP:BRK 1 STATUS CLSD A:BRK 1 FLSHOVR PKPDELAY:BRK 1 FLSHOVR DPO ABRK 1 FLSHOVR PKP ABRK 1 FLSHOVR OPBRK 1 FLSHOVR PKPBRK 1 FLSHOVR DPOBRK 1 FLSHOVR OP ABRK 1 FLSHOVR DPO BBRK 1 FLSHOVR PKP BBRK 1 FLSHOVR OP BBRK 1 FLSHOVR DPO CBRK 1 FLSHOVR PKP CBRK 1 FLSHOVR OP CBRK 1 FLSHOVR SUPV A:BRK 1 STATUS CLSD B:BRK 1 FLSHOVR SUPV B:BRK 1 STATUS CLSD C:BRK 1 FLSHOVR SUPV C:BRK 1 FLSHOVR AMP PKP:BRK 1 FLSHOVR DIFF VPKP:BRK 1 FLSHOVR SIDE 1SRC:BRK 1 FLSHOVR SIDE 2SRC:Enable=1 RUNRUNRUNRUNRUNRUNSRC 1, SRC 2, … , SRC 6SRC 1 SRC 2 SRC 6, , … , , noneVBVbIBBlock: OFF=0VA > PKPFlexLogic operand: On=1FlexLogic operand: Off=0FlexLogic operand: On=1FlexLogic operand: Off=0Phase BlogicPhase BlogicPhase B logicPhase B logicPhase ClogicPhase ClogicPhase C logicPhase C logicFlexLogic operand: On=1FlexLogic operand: Off=0IA > PKPΔVA > PKPVa > PKPVAVaIAVCVcΔ | |VA = VA - VaICSETTING SETTINGSETTINGSSETTINGFLEXLOGIC OPERANDSFLEXLOGIC OPERANDSFLEXLOGIC OPERANDFLEXLOGIC OPERANDSFLEXLOGIC OPERANDSSETTINGSSETTINGSETTINGSETTINGSSETTINGS005 cyclet PKP005 cycle6 cycle