GE Multilin L30 Line Current Differential System 5-2455 SETTINGS 5.8 INPUTS AND OUTPUTS5The DIRECT INPUT 1-1(8) DEFAULT setting selects the logic state of this particular bit used for this point if the local relay hasjust completed startup or the local communications channel is declared to have failed. Setting DIRECT INPUT 1-1(8) DEFAULTto “On” means that the corresponding local FlexLogic operand ( DIRECT I/P 1-1(8) ) will have logic state “1” on relay startup orduring communications channel failure. When the channel is restored, the operand logic state reflects the actual state ofthe corresponding remote direct output.c) DIRECT OUTPUTSPATH: SETTINGS INPUTS/OUTPUTS DIRECT DIRECT OUTPUTSThe relay provides eight direct outputs that are conveyed on communications channel 1 (numbered 1-1 through 1-8) andeight direct outputs that are conveyed on communications channel 2 (numbered 2-1 through 2-8). Each digital point in themessage must be programmed to carry the state of a specific FlexLogic operand. The setting above is used to select theoperand which represents a specific function (as selected by the user) to be transmitted.Direct outputs 2-1 to 2-8 are only functional on three-terminal systems.MESSAGE DIRECT INPUT 2-1DEFAULT: OffRange: Off, OnMESSAGE DIRECT INPUT 2-2DEFAULT: OffRange: Off, On↓MESSAGE DIRECT INPUT 2-8DEFAULT: OffRange: Off, On DIRECT OUTPUTSDIRECT OUTPUT 1-1:OffRange: FlexLogic operandMESSAGE DIRECT OUTPUT 1-2:OffRange: FlexLogic operand↓MESSAGE DIRECT OUTPUT 1-8:OffRange: FlexLogic operandMESSAGE DIRECT OUTPUT 2-1:OffRange: FlexLogic operandMESSAGE DIRECT OUTPUT 2-2:OffRange: FlexLogic operand↓MESSAGE DIRECT OUTPUT 2-8:OffRange: FlexLogic operandNOTE