7- 10SPM Synchronous Motor Protection & Control GE Power Management7.5 PROGRAMMING 7 TESTING AND TROUBLESHOOTING7, Change the existing value of SYNC SLIP to 4.0%. SCROLLKey(s) to select value of 4% and then SELECT/ENTER key toaccept new value, SCROLL DOWN key to move to the STALL TIME setpoint thenSELECT/ENTER to select the setpoint, Change the existing value of STALL TIME to 7 seconds. SCROLLKey(s) to select value of 7s and then SELECT/ENTER key toaccept new value, SCROLL DOWN key to move to the RUNTIME setpoint thenSELECT/ENTER to select the setpoint, Change the existing value of RUNTIME to 1.46 times the stalltime. SCROLL Key(s) to select value of 1.46 and then SELECT/ENTER key to accept new value, SCROLL DOWN key to move to the DC CT PRIM setpoint thenSELECT/ENTER to select the setpoint, Change the existing value of DC CT PRIM to 100A. SCROLLKey(s) to select value of 100 and then SELECT/ENTER key toaccept new value.SCROLL DOWN key to move to the HIGH FIELD setpoint. Thisvalue will remain as is., SCROLL DOWN key to move to the FIELD AMPS setpoint thenSELECT/ENTER to select the setpoint., Change the existing value of FIELD AMPS to 45. SCROLL Key(s)to select value of 45 and then SELECT/ENTER key to accept newvalue, SCROLL DOWN key to move to the FIELD VOLTS setpoint thenSELECT/ENTER to select the setpoint, Change the existing value of FIELD VOLTS to 125. SCROLLKey(s) to select value of 125 and then SELECT/ENTER key toaccept new value., SCROLL DOWN key to move to INC SEQ DLY setpoint thenSELECT/ENTER to select the setpoint, Change the existing value of INC SEQ DLY to 15 seconds.SCROLL Key(s) to select value of 15 and then SELECT/ENTERkey to accept new value.Table 7–2: PROGRAMMING EXAMPLE (Sheet 3 of 4)KEYPRESS DISPLAY COMMENTSENTER SYNC SLIP: 4.0%SCROLL to changeENTER STALL TIME: 40 sENTER to modifyENTER STALL TIME: 7 sSCROLL to changeENTER RUNTIME: 3.00 x STENTER to modifyENTER RUNTIME: 1.46 x STSCROLL to changeENTER DC CT PRIM: 20 AENTER to modifyENTER DC CT PRIM: 100 ASCROLL to changeHIGH FIELD: 10.0 ΩENTER to modifyENTER FIELD AMPS: OFFENTER to modifyENTER FIELD AMPS: 45SCROLL to changeENTER FIELD VOLTS: 25ENTER to modifyENTER FIELD VOLTS: 125SCROLL to changeENTER INC SEQ DLY: 100 sENTER to modifyENTER INC SEQ DLY: 15 sSCROLL to change