8.3The Max Run Timer is set automatically once the unit is cycled between Limits.The Max Run Timer prevents the unit from running continuously in the event of a problem. The MRT’s are setto the time required to run from one limit to the other, plus 5 seconds (nominal). When the MRT is exceeded,the operator stops and will not respond to any command until it is reset by pressing one of the calibrationkeys or by cycling power to the unit.Resetting the MRT (Max Run Timer)OPENCLOSESTOPCALRUN SCROLLSCROLLSETCLEARMAX RUN SETFigure 15TO RESET1) Press CAL/RUN to enter calibration mode.2) Press SCROLL (up or down) until display reads ”MAX RUN TMR > SET.” Figure 15.3) Press SET/CLEAR until display reads ”MAX RUN TMR > CLR.”4) Press CAL/RUN to return to RUN mode.5) Cycle the door between limits.NOTE: The Max Run Timer must be reset each and every time the Travel Limits are adjusted.CAUTION: The MID-STOP feature must be turned off in order to properly set the Max Run Timer.ATTENTION: La fonction MID-STOP doit être désactivée afin de régler correctement la minuterie de coursemaximum.!!Section 8: Optional Operator Setup Procedure