106Advanced Operations6.3.3.10 Function set to TIMER working modeINPUT VALUE Displays the process value read from the selected source after it has been processed by theinternal formula parser (if prompted).FREQ. Control /PID CONTROLTIMERSENSORDefault value: No sourceSelect a probe or create a formula which delivers the process value that is to be processed bythe relay card.OUTPUTS ON HOLDDefault value: NOThere is the opportunity to let the relay 'mark' the sensor configured in the menu SENSOR at theDURATION time. Other sc1000 modules such as other relay cards or current output cards whichaccess data of this sensor read this 'mark' and go into hold. To go into hold means the accessingmodule does not read the latest measurement from the marked sensor but works with the lastmeasurement read before the sensor was marked. To activate this function set this menu toYES. If the sensor shall never let other modules go into hold, set this menu to NO.Note: The setting OUTPUTS ON HOLD always adapts to the DURATION time.YES Adds a check mark to the selected SENSOR at the DURATION time. Other modules (relay card,output card) accessing the probe go into hold mode as soon as they read the probe check mark.NO Sensor does not send other modules into hold modeOFF DURATION(0 s–65535 s)Default value: 30 secondsSets the period of time for turning off the relay in one duty cycle (provided the DUTY CYCLEoption is set to DIRECT).DURATION(0 s–65535 s)Default value: 10 secondsSets the period of time for turning on the relay in one duty cycle (provided the DUTY CYCLEoption is set to DIRECT).OFF DELAY(0 s–999 s)Default value: 5 secondsDelays the check mark of a probe even if DURATION time has expired.The OFF DELAY time starts immediately after the DURATION time is expired.This setting only takes effect if OUTPUTS ON HOLD is set to YES (see OUTPUTS ON HOLDoption).DUTY CYCLE Default value: DIRECTDIRECT Turns the relay ON for the time set in the DURATION menu.Turns the relay OFF for the time set in the OFF DURATION menu.REVERSE Turns the relay OFF for the time set in the DURATION menu.Turns the relay ON for the time set in the OFF DURATION menu.INPUT VALUE Displays the process value read from the selected source.NEXT TOGGLE Indicates the seconds until the relay will toggle.LOG INTERVALDefault value: OFFSets the interval for logging the displayed value into the data logger.Options: OFF, 5min, 10min, 15min, 20min, 30min