20 Secure the electrical wiring with cable ties as shownin the figure in 10.2 . Make sure no external pressure is applied to theterminal connectors. When installing the earth leakage circuit breaker makesure that it is compatible with the inverter (resistant tohigh frequency electrical noise ) to avoid unnecessaryopening ofthe earth leakage circuit breaker. As this unit is equipped with an inverter, installing aphase advancing capacitor not only will deterioratepower factor improvement effect, but also may causecapacitor abnormal heating accident due to high-frequency waves. Therefore, never install a phaseadvancing capacitor.CAUTIONBe sure to install the required fuses or circuitbreakers.10.2. Connecting power supply and inter-unit wiring Connect and fix the power supply cable, indoor-outdoor connection cable as following:Power supply:380-415V,3N~,50/60HzOutdoor unitterminal blocksIndoor unitterminal blocksFor three phase power supply models:1U125S2SN1FB, 1U140S2SN1FB,1U140S2SP1FB.Power supply cable:For 1U125S2SN1FB/1U140S2SN1FB/1U140S2SP1FBH05RN-F 5G 2.5mm2,Indoor and outdoor connection cable:H05RN-F 4G 2.5mm2” If the indoor and outdoor unitconnection cable length L satisfied condition 40m<L<55m, please change the connection cablesspecification to H07RN-F 4G 4.0mm2. If the indoorand outdoor unit connection cable length L satisfiedcondition 55m1 L1 75m, please change the connectioncables specification to H07RN-F 4G 6.0mm2Power supply:1PH,220-240V~,50/60HzOutdoor unitterminal blocks1U105S2SS1FA1U125S2SN1FA1U140S2SN1FA1U140S2SP1FAIndoor unitterminal blocksFor single phase power supply models:1U105S2SS1FA,Power supply cable: H05RN-F 3G 4.0mm21U125S2SN1FA,1U140S2SN1FA,1U140S2SP1FAPower supply cable: H05RN-F 3G 6.0mm2Indoor and outdoor connection cable: H05RN-F 4G 2.5mm2If the indoor and outdoorunIt connection cable length L satisfied condition 40m<L<55m, please change the connection cablesspecification to H07RN-F 4G 4.0mm2. If the indoorand outdoor unit connection cable length L satisfiedcondition 55m, L, 75m, please change the connectioncables specification to H07RN-F 4G 6.0mm2 Fix the cable with the clip to prevent slide.Clip ClipOutdoor-indoor unitconnection cablePower supply cable Secure the cable to the stop valve attachment plateso that it does not slide. When cables are routed from the unit, a protectionsleeve for the conduits (PG-insertions) can beinserted at the knock-out hole. When you do not use a wire conduit, be sure toprotect the wires with vinyl tubes to revent the edge ofthe knock-out hole from cutting the wires. Follow the electric wiring diagram for electrical wiringworks.1U125S2SN1FB1U140S2SN1FB1U140S2SP1FB