INSTALLATION MANUAL FOR OUTDOOR UNITAir outAir inAir inAir in Mounting and maintenancesurface32WarningSelection of installation siteIt should be installed at places where it is firm enough to withstand the weight of the air conditioner toprevent falling.Typhoon and earthquake prevention. It should be installed according to specific requirements.Inasppropriate installation may lead to accidents.Note: Obstacles should be 2000mm off the top of the out-door unit. Obstacles nearby should be 400mm lowerthan the top of the unit.1. HandingAs there is no protective package for the outdoor unit,sothe following points merit attention:(1) When forklift is used, insert the fork into the holes inthe base plate.(2) When crane is used, lift the unit with 4 pieces of steelrope with diameter above 6 mm.(3) Put protective materials between the cable and theunit to prevent deformation and damage of the surface.2.Mounting(1) The distance between two connectionsmust not beless than 20mm.(1)During installation, connect the outdoor unit and alignthe mounting surface(See the figure on the right).Mountthe electric distribution device on the external side ofthe unit in accordance to the installation instructions forelectric distribution device.(2)To ensure good performance of the machine and facili-tate installation and maintenance, adequate space mustbe reserved (See figure on the right).Installtion space20mm 20mmM12 foundation bolt(4 pieces each)Steel ropeProtective cushionBase plate20 Steel ropeA vertical view of the outdoor unitAbove 300mm20mm 20mm 20mm Above 20mm1000mmAboveAbove(front side) Above