SAFETY PRECAUTIONS51. Applicable ambient temperature range:The machine is adaptive in following situationCoolingHeatingIndoorIndoorOutdoorOutdoorMaximum:Minimum:Maximum:Minimum:Maximum:Minimum:Maximum:Minimum:D.B / W.BD.B / W.BD.B / W.BD.B / W.BD.B / W.BD.B / W.BD.BD.BD.B32 / 2318 / 14-7 / -824 / 1843151527/ 262. If the supply cord is damaged, it must be replaced by the manufacturer or its service agentor a similar qualified person.3. If the fuse on PC board is broken please change it with the type of T. 3.15A /2500.4. The wiring method should be in line with the local wiring standard.5. The power cable and connecting cable are self-provided. The power cable should be5x5.0mm2 .The connecting cable should be 4x2.0mm2.All the cables shall have got the European authentication certificate. During installa-tion, when the connecting cables break off, it must be assured that the grouding wire isthe last one to be broken off.6. The breaker of the air conditioner should be all-pole switch; and the distance between itstwo contacts should be no less 3mm.7. The indoor unit installation height is at least 2.5m.Installation and maintenance must be meet the local installation and miantenance instructions andshould operate by the experienced special installation and maintenance technicians .itherwise wedonít take any duty of the units damage or injure to the person caused by improper operation.NOTE!1.The sharp edges and corners and coil surface have the danger to injury ,should avoid of them;2.Itís very danger to remove the units and power supply wire.because it can cause injury and death .Cut off all the power supply before mintenance.WARNING!