AU48NFIBIA troubleshooting:ReconnectReset addressnoyes1.Communication failureIs indoor unit addressproperly set? Withoutrepetition?nononoyesyesAre communication terminals ofindoor and outdoor unitssecurely connected?Is shielded wireused forcommunication?Use shielded wire. Shield layershould be grounded at singlepointAre communication wireand power cable setseparately?wiring SeparatelyyesyesyesIs there external signalinterference? Eliminate interferenceIs indoor mainboard poorlywelded?nononoyesReplace indoor PCBAre communication resistance andcapacitor of indoor PCB correct? SeeNOTEReplace indoor PCBCheck outdoor mainboard. Makenecessary replacementNOTE: 1. R49.R50 resistor in AS072-182FCBHA circuit and R40.R41 resistor in AE072-242FCBKAcircuit have a resistance of 100 K instead of 47K AS models and C28~C30 of AE models use 104polyester resistors.Is number of indoor unitsindicated by testing boardcorrect? Changeable?yesyes Communication normalNote: For outdoor units before December 2004, in the event of 3 IPM or high currentfaults, outdoor unit will stop signal transmission to indoor unit. Indoor unit will displaycommunication fault.Normally, testing board will indicate number of indoor units. The number is fixed.Wired controller display: E9; 4 flashes of indoor TIMER light of models with remotecontrol-179-