I-7088I-7088 User Manual, Rev: A1.0162.1. %AANNTTCCFFDescription:This command is used to set the configuration of a module.Syntax:%AANNTTCCFF[CHKSUM](CR)% Delimiter characterAA The address of the module to be configured inhexadecimal format (00 to FF)NN The new address of the module in hexadecimal format(00 to FF)TT The new type code, see Section 1.7 for detailsCC The new Baud Rate code, see Section 1.7 for details.For the I-7088, the rear slide switch must be moved tothe INIT position in order to change Baud Rates. SeeSection A.1 for details.FF The command used to set the data format, checksum,and filter settings (Section 1.7). For the I-7088, therear slide switch must be moved to the INIT positionin order to change the checksum setting. See SectionA.1 for details.Response:Valid Command: !AA[CHKSUM](CR)Invalid Command: ?AA[CHKSUM](CR)! Delimiter for a valid command? Delimiter for an invalid command(If the Baud Rate or checksum settings are changedwithout switching the rear slide switch to the INITposition, the module will return an invalid command.)AA The address of the module in hexadecimal format (00to FF)