M-7026M-7026 User Manual Rev: 1.5 Date: 2016/03/10 1032.46 ~AADVVDescription:This command is used to set the Digital Input and Digital Output configurationfor a specified module.Syntax:~AADVV[CHKSUM](CR)~ Delimiter characterAA The address of the module to be set in hexadecimal format (00 to FF)D The command to set the Digital Input and Digital Output configurationVV A two-digit hexadecimal value representing the miscellaneoussettings, as indicated in the tables below:7 6 5 4 3 2 1 0Reserved OA IAKey DescriptionIA Bit 0: Specifies the active state of the Digital Input signal0: An input value of 0 indicates that the input is floatingAn input value of 1 indicates that the input is connected to aCOM port1: An input value of 0 indicates that the input is connected to aCOM portAn input value of 1 indicates that the input is floatingOA Bit 1: Specifies the active state of the Digital Output signal0: An output value of 0 indicates that the output is inactiveAn output value of 1 indicates that the output is active1: An output value of 0 indicates that the output is activeAn output value of 1 indicates that the output is inactiveResponse:Valid Command: !AA[CHKSUM](CR)Invalid Command: ?AA[CHKSUM](CR)! Delimiter character to indicate a valid command? Delimiter character to indicate an invalid commandAA The address of the responding module in hexadecimal format (00 toFF)There will be no response if the command syntax is incorrect, there is acommunication error, or there is no module with the specified address.Examples:Command: ~$01D01 Response: !01