M-7026M-7026 User Manual Rev: 1.5 Date: 2016/03/10 1442.70 @AARHCiDescription:This command is used to read the high alarm limit for a specific Analog Inputchannel of a specified module.Syntax:@AARHCi[CHKSUM](CR)@ Delimiter characterAA The address of the module to be read in hexadecimal format (00 toFF)RH The command to read the high alarm limit for the Analog InputchannelCi The Analog Input channel to be read, zero based (0-5)Response:Valid Command: !AA(Data)[CHKSUM](CR)Invalid Command: ?AA[CHKSUM](CR)! Delimiter character to indicate a valid command? Delimiter character to indicate an invalid commandAA The address of the responding module in hexadecimal format (00 toFF)(Data) The high alarm limit for the specified Analog Input channel inEngineering Units format. See Section 1.9.4 for details of the dataformat.There will be no response if the command syntax is incorrect, there is acommunication error, or there is no module with the specified address.Examples:Command: @01HI+08.000C0 Response: !01Sets the high alarm limit for Analog Input channel 0 of module 01 to+08.000 (+8.0 V) and returns a response indicating that the commandwas successful.Command: @01RHC0 Response: !01+08.000Reads the high alarm limit for Analog Input channel 0 of module 01 andreturns a response indicating that the command was successful, and thatthe high alarm limit is +08.000 (+8.0 V).Command: @01RHCF Response: ?01Attempts to read the high alarm limit for Analog Input channel 15 ofmodule 01, but returns a response indicating that the command wasunsuccessful because Analog Input channel 15 does not exist.Related Commands:Section 2.55 @AACHCi. Section 2.60 @AADACi, Section 2.63 @AAEATCi,Section 2.64 @AAHI(Data)Ci, Section 2.66 @AARACi, Section 2.67