18INSTALLATIONi-mini - Installation and ServicingFLUE OUTLET100mmEdge of turretto outside face of wall plus44mm = flue lengthCentre of turret to edge of turret = 100mmTurret has a flue insertion of 30mmThe compressed outer wall seal has protruding wall to seal mounting lip - 14mmFrom centreline of turret to wall. Rear mount 155mm, side (including clearance) 200mmNOTESREARFitto wallAWALLEdge of turretto outside face of wall plus44mm = flue lengthFlue length measured from outer terminal lipto end of outer flueA + 44mmREARFitto wallinc. Standoff FrameAWALLEdge of turretto outside face of wall plus44mm = flue lengthSIDEFitto wallAWALLMinimum clearance 5mm14 DETERMININg ThE FLUE LENgTh aND FLUE paCKs REqUIRED, CONT’DShows the flue required when measured from outside edge of turret to the outside face of the wall (to obtain cut length add 44mm)Minimum & Maximum finished flue lengths obtainable (dimension ‘A’ +44mm)horizontal Flue Terminal(600mm long) B packTelescopic Flue B pack horizontal FlueTerminal (1000mm long)B pack (Telescopic)horizontal Flue Terminal(1000mm long) B pack(Telescopic) Cut 75mmMinimum Maximum Minimum Maximum Minimum Maximum Minimum MaximumB pack (standard) 171 556 286 484 601 816 526 741Plus 1 (1m D pack) 1121 1506 1236 1434 1551 1766 1476 1691Plus 2 (1m D pack) 2071 2456 2186 2384 2501 2716 2426 2641Plus 3 (1m D pack) 3021 3406 3136 3334 3451 3666 3376 3591Plus 4 (1m D pack) 3971 4356 4086 4284 4401 4616 4326 4541Plus 5 (1m D pack) 4921 5306 5036 5234 5351 5566 5276 5491Plus 6 (1m D pack) 5871 6256 5986 6184 6301 6516 6226 6441Plus 7 (1m D pack) 6821 7206 6936 7134 7251 7466 7176 7391Plus 8 (1m D pack) 7771 8186 7886 8084 8201 8416 8126 8341Plus 9 (1m D pack) 8721 9000 8836 9000 9000 9000 9000 9000Max output 30 kWMax output 24 kWFIgURE 1FIgURE 2Note. Maximum permissibleflue length is measured fromcentre line of appliance flueoutlet to outside wall face.Note; Telescopic flue B Pack or attached “D” pack extensions do not need to be cut between minimum and maximum valuesshown above (except where specified). Horizontal Flue Terminal (600mm long) B Pack flue will require cutting on valuesbelow maximum values shown in the table above.If using the 2000mm D Pack , the maximum usable length per extension is 1950mmIf using the 500mm D Pack, the maximum usable length per extension is 450mm.