pool, spa or hot tub structure and to all electricalcomponents and equipment associated with thepool/spa water circulation system.2. The bonding must be accomplished by using asolid copper conductro, No. 8 AWG or larger.In Canada No. 6 AWG or larger must be used.Bond the motor using the external bonding lugprovided on the motor frame.To avoid the risk of property damage, severepersonal injury, and/or death, always disconnectthe power source before working on a motor or itsconnected load.WARNINGTo avoid the risk of property damage, severe per-sonal injury, and/or death, make sure that the con-trol switch or time clock is installed in an accessiblelocation so that in the event of an equipment failureor a loose plumbing fitting the equipment can beturned off. This location must not be in the samearea as the pool pump, filter, and other equipment.WARNINGThe pump must be permanently connected to adedicated electrical circuit. No other equipment,lights, appliances or outlets may be connected tothe pump circuit, with the exception of devices thatmay be required to operate simultaneously with thepump, such as a chlorinating device or heater.WARNING3.2.3 Electrical WiringTo avoid risk of property damage, severe personalinjury, or death, always ground before connecting toan electrical power supply.WARNING1. The pump motor must be securely andadequately grounded using the green screwprovided. Ground before attempting to connectto an electrical power supply. Do not ground toa gas supply line.2. Wire size must be adequate to minimize voltagedrop during the start-up and operation of thepump. See Table 2 for recommended wire sizes.RECOMMENDED MINIMUM WIRE SIZE FOR SHP PUMPS*Distance from Sub-Panel 0-50 Feet 50-100 Feet 100-150 Feet 150-200 FeetPump ModelInverse - Time CircuitBreaker or BranchFuse AMPsClass: CC, G, H, J, K,RK, or TVoltage Voltage Voltage Voltage230VAC 115VAC 208-230 VAC 115 VAC 208-230 VAC 115 VAC 208-230 VAC 115 VAC 208-230 VAC 115 VACSHPF .50HP/SHPM .75HP 15A 15A 14 12 12 8 10 6 8 6SHPF .75HP/SHPM 1.0HP 15A 15A 14 12 12 8 10 6 8 6SHPF 1.0HP/SHPM 1.5HP 15A 20A 12 10 10 8 8 6 6 4SHPF 1.0-3PH 15A N/A 14 N/A 12 N/A 10 N/A 8 N/ASHPF 1.5HP/SHPM 2.0HP 15A N/A 12 N/A 10 N/A 8 N/A 6 N/ASHPF 1.5-3PH 15A N/A 12 N/A 10 N/A 8 N/A 6 N/ASHPF 2.0HP/SHPM 2.5HP 15A N/A 12 N/A 8 N/A 6 N/A 6 N/ASHPF 2.0-3PH 15A N/A 12 N/A 10 N/A 8 N/A 6 N/ASHPF 3.0HP 20A N/A 10 N/A 8 N/A 6 N/A 4 N/ASHPF 3.0-3PH 15A N/A 12 N/A 8 N/A 6 N/A 6 N/ASHPF 5.0 25A N/A 10 N/A 8 N/A 6 N/A 6 N/ASHPF 1.0HP-2-SPD (1) 15A N/A 12 N/A 10 N/A 8 N/A 6 N/ASHPF 1.5HP-2-SPD (1) 15A N/A 12 N/A 10 N/A 8 N/A 6 N/ASHPF 2.0HP-2-SPD (1) 15A N/A 12 N/A 8 N/A 6 N/A 6 N/ASHPM 1.5HP-2-SPD (1) 15A N/A 12 N/A 10 N/A 8 N/A 6 N/ASHPM 2.0HP-2-SPD (1) 15A N/A 12 N/A 10 N/A 8 N/A 6 N/ASHPM 2.5HP-2-SPD (1) 15A N/A 12 N/A 8 N/A 6 N/A 6 N/A*Assumes three (3) copper conductors in a buried conduit and 3% maximum voltage loss in branch circuit. All National Electrical Code® (NEC®) and local codesmust be followed. Table shows minimum wire size and branch fuse recommendations for a typical installation per NEC.(1) Two-speed pumps are not rated for use with 208 VAC.Table 2. Recommended Minimum Wire SizePage 9ENGLISHJandy ® Pro Series Stealth ™ Pumps | Operation Manual