GB - 29Annex B• Integral solid state short circuit protection does not provide branch circuit protection.Branch circuit protection must be provided in accordance with the Manufacturer In-structions, National Electrical Code and any additional local codes, or the equivalent.Table for input fusing of inverters F5 – A – housing, stand-alone drive units:Inverter Input Voltage UL248 FuseClass J or RK5 * )UL248 FuseClass CC * )[V] [A] [A]05F5 240 1ph 10 1005F5 240 3ph 6 505F5 400/480 3ph 5 507F5 240 1ph 15 2007F5 240 3ph 10 1007F5 400/480 3ph 6 609F5 400/480 3ph 10 10*) The voltage rating of the Class rated fuses shall be at least equal to the voltage ratingof the Drives.Branch Circuit Protection: Type E Self Protected Manual Motor Controllers forinverters F5–A housing, stand-alone drive units::Cat. No. Drive Input rating Self Protected Manual MotorController Type and manufac-turerSelf Protected Man-ual Motor Controllerrating05F5 240V 1ph PKZMO-10E, Eaton Industries 230V/1ph, 1.5 hp05F5 240V 3ph PKZMO-6.3E, Eaton Industries 230V/3ph, 1.5 hp07F5 240V 1ph PKZMO-16E, Eaton Industries 230V/1ph, 2 hp07F5 240V 3ph PKZMO-10E, Eaton Industries 240V/3ph, 3 hpCat. No. Drive Input rat-ing #Self Protected Manual MotorController Type and manufac-turerSelf Protected Man-ual Motor Controllerrating05F5 400/480V 3ph PKZMO-10E, Eaton Industries 480Y/277V, 3 hp07F5 400/480V 3ph PKZMO-10E, Eaton Industries 480Y/277V, 7.5 hp09F5 400/480V 3ph PKZMO-10E, Eaton Industries 480Y/277V, 7.5 hp# all Drives series which use a Self Protected Motor Controller rated 480Y/277V are suitablefor 480Y/277V sources only.