ID: Fb01Name: FBS ConfigMeaning Some configuration settings of the F5 PROFINET operatorParameter number (PNU): 0281hSubindex: 0Data type: Uint16Coding: b15…b7 b6 b5 b4 b3 b2 b1 b0xxx Pnet_SubIdx_LinearEnable_PDMapUse_De-fault_PDMapPDAPI_DisableDisable_NetX_ResetSync-Mode_EnableIRT_En-ablebit0 = 1 IRT_Enable: In preparationbit1 = 1 SyncMode_Enable: Enables the internal cyclic communication.bit2 = 1 Disable NetX-Reset: At fundamental problems when starting thePROFINET firmware, the CPU of the PROFINET operator cancarry out a hardware reset of the PROFINET ASIC (NetX). Thisfunction can be disabled via this bit.bit3 = 1 PDAPI_Disable: For the function to be able to exchange acy-clic data with a standard Siemens S7 PROFINET controller toPROFIDRIVE Base Mode Parameter Access, the F5 PROFINEToperator has a second API with value = 3A00h. The module withthe name ,ProfiDrive_PAP' is assigned to this API. Via this bit thecomplete functionality of the API = 3A00h can be disabled with themodule ,ProfiDrive_PAP'. In this case the acyclic communicationto PROFIDRIVE Base Mode-Parameter-Access can be executedalso via the standard API with value = 0.bit4 = 1 The default PD mapping is written when starting the software tothe drive converter, if bit5 = 1.bit4 = 0 The non-volatile stored PD mapping in the operator (see Fb28 toFb31) is written to the drive converter at boot-up, if bit5 = 1.bit5 = 0 Writing the PD mapping to the drive converter control is deactivat-ed at boot-up.bit5 = 1 Writing the PD mapping to the frequency inverter control is activat-ed at boot-up.bit6 = 1 When addressing the parameters to PROFINET acyclic data thesubindex is not bit-coded, but linearly coded.bit7 = 1 Activation of the PROFINET alarm signals. When the alarm isactivated, the operator monitors the value of the drive converterparameter ru00 „inverter state“ (see chapter 3.11).Standard value: 0Note: A new value is stored non-volatile, but only active at the next switch on.44PARAMETER DEScRIPTION